Adding A Smartli; Setting Smartli Monitoring Parameters (Modbus Tcp); Creating A Smartli On The Neteco - Huawei iMaster NetEco V600R021C10 Device Installation And Commissioning Manual

Table of Contents

Advertisement

iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
Step 8 Click
Step 9 Click Connection test to start the connection test.
----End

6.4.8 Adding a SmartLi

6.4.8.1 Setting SmartLi Monitoring Parameters (Modbus TCP)

Before connecting the SmartLi to the NetEco, set monitoring parameters such as
the IP address on the SmartLi.
Prerequisites
Context
SmartLi model: SmartLi-512V-80AH-F-01
Procedure
Step 1 On the SmartLi LCD home screen, tap Settings.
Step 2 Enter the SmartLi password.
Step 3 Choose Communication.
1.
2.
----End

6.4.8.2 Creating a SmartLi on the NetEco

This section describes how to create a SmartLi on the NetEco.
Prerequisites
Issue 02 (2021-05-12)
on the toolbar to save the device information.
You have obtained the IP address, subnet mask, and default gateway planned
for the SmartLi.
The SmartLi is powered on.
NO TE
The preset password is 000001.
Set IP address assign to Manual, and set IP address, Subnet mask, and
Gateway.
Set ModbusTCP encryption to Enable.
NO TE
If Modbus TCP encryption is disabled on the device, SSL connection must be disabled
on the NetEco.
You have the operation rights for Planning Configuration.
You have created a management domain for the device to be added on the
Planning Configuration page.
Copyright © Huawei Technologies Co., Ltd.
6 Adding Devices
219