Huawei iMaster NetEco V600R021C10 Device Installation And Commissioning Manual page 172

Table of Contents

Advertisement

iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
7.
Issue 02 (2021-05-12)
Running
Parameter
Modbus Config
Alarm Threshold
Settings
iBAT Parameters
Config
Basic Information
Hall Reverse
Config
IScan Register
Config
Parallel Comm
TLS Config
On the System Settings page, set Alarm Parameters, Time, IP Address,
Certificate Management, Battery Curve, NetEco, and Parallel Net Join
Configuration Information.
Figure 6-13 Alarm Parameters
Figure 6-14 Time
Copyright © Huawei Technologies Co., Ltd.
Description
Set ModbusTCP encryption and ModbusTCP
authentication parameters, which should be consistent
with the setting of Connection Mode on the NetEco.
Set the battery internal resistance, charge overcurrent,
charge overvoltage, and bias alarm thresholds.
Set the iBAT intelligent hibernation and battery
undervoltage protection threshold.
If a BCB is configured, set BCB configuration to Done
and Batt. abnormal BCB trip to Enable.
If the Hall effect sensor is reversely installed, you can
set reverse connection to correct it.
Enable or disable iScan registration.
Enable or disable the TLSv1.1 protocol for parallel
communication
6 Adding Devices
161