6.4.9 Adding a CO Power Module

6.4.9.1 Setting Monitoring Parameters for the TP483000D and TP482000B

Before connecting a TP483000D or TP482000B to the NetEco, set the IP address
on the TP483000D or TP482000B.
Prerequisites
Procedure
Step 1 On the TP483000D or TP482000B LCD, choose Setting Wizard > Comm Para.
Step 2 Set IP Address, Subnet Mask, and Gateway based on the planned data.
----End

6.4.9.2 Creating a Power Module on the NetEco

This section describes how to create a CO power module on the NetEco.
Prerequisites
Procedure
Step 1 Log in to the NetEco client.
Step 2 On the main menu, choose Device Management > Configuration > Planning
Configuration.
Step 3 Choose the management domain where you want to create a device from the
navigation tree on the left.
Step 4 In the lower-left corner of the page, click the Device tab.
Issue 02 (2021-05-12)
Description
Re-authentication password for the NetEco and device. The
default value is Modifyme_123.
on the toolbar to save the device information.
You have obtained the IP address planned for the TP483000D or TP482000B.
The TP483000D or TP482000B has been powered on and is running properly.
You have the operation rights for Planning Configuration.
You have created a management domain for the device to be added on the
Planning Configuration page.