Routine Maintenance For The Smoke Detector - Huawei iMaster NetEco V600R021C10 Device Installation And Commissioning Manual

Table of Contents

Advertisement

iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
Table 7-4 Routine Maintenance for VCN
Item
Check the
VCN indicator.

7.1.1.4 Routine Maintenance for the Smoke Detector

Table 7-5 Routine Maintenance for the Smoke Detector
Item
Smoke
detector
indicator
Smoke
detector
availabilit
y
Issue 02 (2021-05-12)
Maintena
Method
nce
Interval
Monthly
Observe the
VCN indicator.
Maintena
Method
nce
Interval
Monthly
Observe and
check whether
the indicator
on the smoke
detector is
normal.
Monthly
Use a
dedicated test
instrument or
a smoke
generator to
test the
smoke
detector. Blow
smoke to the
smoke
detector probe
and observe
the indicator
status.
Copyright © Huawei Technologies Co., Ltd.
7 Device Maintenance
Expected
Result
The VCN
indicator is
steady green.
Expected
Exception Handling
Result
The indicator
If the indicator
blinks once
blinks twice every 6
every 6
seconds or does not
seconds. (The
blink, the smoke
interval varies
detector is faulty or
with sensors.
the cables are not
See the
properly connected.
product
Check the cables or
instructions.)
replace the smoke
detector.
● If the
● If the smoke
smoke
density is below
density is
the alarm
below the
threshold but the
alarm
alarm indicator
threshold,
blinks twice every
the alarm
6 seconds, the
indicator
smoke detector is
blinks once
faulty. Replace
every 6
the smoke
seconds.
detector.
● If the
● If the smoke
smoke
density exceeds
density
the alarm
exceeds the
threshold but the
alarm
alarm indicator is
threshold,
not steady on,
the alarm
replace the
indicator is
smoke detector.
steady on.
Exception
Handling
See the
delivered
documents.
277