Huawei FusionModule500 User Manual
Huawei FusionModule500 User Manual

Huawei FusionModule500 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

Quick Links

FusionModule500 Smart Mini Data Center
V100R021C00
User Manual
Issue
02
Date
2020-12-25
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei FusionModule500

  • Page 1 FusionModule500 Smart Mini Data Center V100R021C00 User Manual Issue Date 2020-12-25 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    FusionModule500 Smart Mini Data Center User Manual About This Document About This Document Purpose This document describes the FusionModule500 Smart Mini Data Center (smart module for short) in terms of its installation, commissioning, operation, and maintenance. Intended Audience This document is intended for: ●...
  • Page 4 FusionModule500 Smart Mini Data Center User Manual About This Document Symbol Description Supplements the important information in the main text. NOTE is used to address information not related to personal injury, equipment damage, and environment deterioration. Change History Changes between document issues are cumulative. The latest document issue contains all updates made in previous issues.
  • Page 5: Table Of Contents

    FusionModule500 Smart Mini Data Center User Manual Contents Contents About This Document........................ ii 1 Safety Information........................1 1.1 General Safety..................................1 1.2 Personnel Requirements............................... 4 1.3 Electrical Safety..................................4 1.4 Installation Environment Requirements.......................... 6 1.5 Mechanical Safety................................... 8 1.6 Cooling System Safety.................................10 1.7 Battery Safety..................................
  • Page 6 FusionModule500 Smart Mini Data Center User Manual Contents 3.4.2.3 Alarm....................................28 3.4.2.4 Historical Data Query..............................29 3.4.2.5 Linkage Control................................29 3.4.3 Key Hardware Devices..............................29 3.4.3.1 ECC800-Pro..................................29 3.4.3.1.1 Product Configuration............................... 29 3.4.3.1.2 Main Control Module..............................31 3.4.3.1.3 Power Module................................40 3.4.3.2 Environment Monitoring System..........................
  • Page 7 FusionModule500 Smart Mini Data Center User Manual Contents 4.2.4.3 Installing an Indoor Unit............................. 76 4.2.4.4 Exhausting Nitrogen from an Indoor Unit......................77 4.2.4.5 Installing an Outdoor Unit............................79 4.2.4.5.1 Installation Requirements............................79 4.2.4.5.2 Securing an Outdoor Unit............................80 4.2.4.6 Installing a Low-Temperature Component......................81 4.2.4.7 Connecting Pipes................................
  • Page 8 FusionModule500 Smart Mini Data Center User Manual Contents 4.3.4.5 Connecting a Cable to the WLDS900 Water Sensor..................149 4.4 Verifying the Installation..............................150 5 Power-On Commissioning....................153 5.1 Power-On Commissioning for the Power Supply and Distribution System........... 153 5.1.1 UPS Power-On Commissioning..........................154 5.1.2 Connecting the Lithium Battery Supply........................
  • Page 9 FusionModule500 Smart Mini Data Center User Manual Contents 5.3.13 (Optional) NetEco Management..........................215 5.3.13.1 NetEco6000 Management............................. 216 5.3.13.1.1 Connecting a Communications Cable......................216 5.3.13.1.2 Setting NetEco Parameters..........................216 5.3.13.1.3 Obtaining the NetEco Software License......................217 5.3.13.1.4 Powering On a Server............................218 5.3.13.1.5 Logging In to the NetEco Client........................218 5.3.13.1.6 Loading a NetEco License...........................
  • Page 10 FusionModule500 Smart Mini Data Center User Manual Contents 6.4.3.3 Replacing an ECC800-Pro Antenna........................274 6.4.3.4 Replacing a SIM Card..............................275 6.4.3.5 Replacing a Camera..............................276 6.4.3.6 Replacing a VCN510..............................278 6.4.3.7 Replacing an IVS1800..............................280 6.4.3.8 Replacing a Hard Disk for the IVS1800....................... 281 6.4.3.9 Replacing a T/H Sensor (33010516)........................
  • Page 11: Safety Information

    The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
  • Page 12 FusionModule500 Smart Mini Data Center User Manual 1 Safety Information General Requirements ● Do not install, use, or operate outdoor equipment and cables (including but not limited to moving equipment, operating equipment and cables, inserting connectors to or removing connectors from signal ports connected to outdoor facilities, working at heights, and performing outdoor installation) in harsh weather conditions such as lightning, rain, snow, and level 6 or stronger wind.
  • Page 13 FusionModule500 Smart Mini Data Center User Manual 1 Safety Information ● All cable holes should be sealed. Seal the used cable holes with firestop putty. Seal the unused cable holes with the caps delivered with the cabinet. The following figure shows the criteria for correct sealing with firestop putty.
  • Page 14: Personnel Requirements

    Do not power on the equipment before it is installed or confirmed by professionals. 1.2 Personnel Requirements ● Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations. ●...
  • Page 15 FusionModule500 Smart Mini Data Center User Manual 1 Safety Information General Requirements Use dedicated insulated tools when performing high-voltage operations. AC and DC Power D ANGER Do not connect or disconnect power cables with power on. Transient contact between the core of the power cable and the conductor will generate electric arcs or sparks, which may cause fire or personal injury.
  • Page 16: Installation Environment Requirements

    FusionModule500 Smart Mini Data Center User Manual 1 Safety Information ● Do not perform any improper operations, for example, dropping cables directly from a vehicle. ● When selecting, connecting, and routing cables, follow local safety regulations and rules. NO TICE...
  • Page 17 FusionModule500 Smart Mini Data Center User Manual 1 Safety Information vents, or feeder windows of the equipment room. Ensure that no liquid enters the equipment to prevent faults or short circuits. ● If any liquid is detected inside the equipment, immediately disconnect the power supply and contact the administrator.
  • Page 18: Mechanical Safety

    FusionModule500 Smart Mini Data Center User Manual 1 Safety Information 1.5 Mechanical Safety Hoisting Devices ● Do not walk under hoisted objects. ● Only trained and qualified personnel should perform hoisting operations. ● Check that hoisting tools are available and in good condition.
  • Page 19 FusionModule500 Smart Mini Data Center User Manual 1 Safety Information ● When climbing a ladder, take the following precautions to reduce risks and ensure safety: – Keep your body steady. – Do not climb higher than the fourth rung of the ladder from the top.
  • Page 20: Cooling System Safety

    FusionModule500 Smart Mini Data Center User Manual 1 Safety Information ● When moving the equipment by hand, wear protective gloves to prevent injuries. ● Move or lift the equipment by holding its handles or lower edges. Do not hold the handles of modules (such as power supply units, fans, and boards) that are installed in the equipment because they cannot support the weight of the equipment.
  • Page 21: Battery Safety

    FusionModule500 Smart Mini Data Center User Manual 1 Safety Information Refrigerant Frostbite Refrigerant leakage may cause frostbite. Take protective measures (for example, wear antifreeze gloves) when handling refrigerant. Storage and Recycling ● Do not store devices near a heat source or under direct sunshine.
  • Page 22 NO TICE To ensure battery safety and battery management accuracy, use batteries provided with the UPS by Huawei. Huawei is not responsible for any battery faults caused by batteries not provided by Huawei. Battery Installation Before installing batteries, observe the following safety precautions: ●...
  • Page 23 FusionModule500 Smart Mini Data Center User Manual 1 Safety Information Lead-acid batteries emit flammable gas when used. Ensure that batteries are kept in a well-ventilated area and take preventive measures against fire. Battery Leakage NO TICE Battery overheating causes deformation, damage, and electrolyte spillage.
  • Page 24: Others

    FusionModule500 Smart Mini Data Center User Manual 1 Safety Information ● Do not throw a lithium battery in fire. ● When maintenance is complete, return the waste lithium battery to the maintenance office. 1.8 Others ● Exercise caution when shutting down the smart cooling product. Doing so may cause equipment and room overheating, which will damage the equipment.
  • Page 25: Overview

    To meet the requirements for customers' growing services, Huawei launches the FusionModule500 that can be rapidly deployed and flexibly expanded. The FusionModule500 is positioned as a smart module solution and occupies about 10 . It is mainly used in the equipment rooms of county-level governments, bank business outlets, and small and medium-sized enterprises.
  • Page 26 FusionModule500 Smart Mini Data Center User Manual 2 Overview Figure 2-1 Position of the FusionModule500 in the financial industry (1) FusionModule5000 (2) FusionModule2000 (3) FusionModule800 (4) FusionModule500 Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 27: Features

    FusionModule500 Smart Mini Data Center User Manual 2 Overview Figure 2-2 Position of the FusionModule500 for governments (1) FusionModule5000 (2) FusionModule2000 (3) FusionModule800 (4) FusionModule500 2.2 Features High Integration The smart module integrates the cabinet system, power supply and distribution system, cooling system, management system, surge protection and grounding system, and integrated cabling system to provide a comprehensive solution.
  • Page 28: Typical Application Scenarios And Configurations

    FusionModule500 Smart Mini Data Center User Manual 2 Overview High Scalability ● The modular design allows the smart module to be flexibly configured so that fast capacity expansion can be achieved. ● The smart module provides redundant power ports and communications ports for future expansion.
  • Page 29 FusionModule500 Smart Mini Data Center User Manual 2 Overview Table 2-1 Typical configuration Item Specifications Cabinet dimensions (H x 2000 mm x 600 mm x 1350 mm W x D) Power backup time 60–240 minutes Power distribution UPS2000-G, lithium battery, and rPDU...
  • Page 30: System Architecture

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture System Architecture 3.1 Structural System The cabinet possesses the following features: ● The cabinet houses standard 19-inch wide devices. ● Half-height rPDUs can be vertically installed at the rear of the cabinet.
  • Page 31: Power Supply And Distribution System

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture 3.2 Power Supply and Distribution System 3.2.1 Overview The UPS supplies uninterruptible power to IT loads by means of lithium batteries when the external power supply fails. Figure 3-1 Power distribution principles in the UPS scenario Issue 02 (2020-12-25) Copyright ©...
  • Page 32: Kva Ups

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture 3.2.2 6 kVA UPS Figure 3-2 Front and rear views of a 6 kVA UPS (1) Liquid crystal display (2) Maintenance bypass (3) Optional card slot (LCD) (MBS) port (4) Battery management...
  • Page 33: Power Distribution Subrack

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture NO TE ● The RS485 port supports only the Modbus RTU protocol. ● a: The USB port supports the serial port communication protocol. The USB port can be used to export logs and send serial port commissioning commands.
  • Page 34: Optional) Rpdu

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Item Specifications Output frequency 50 Hz/60 Hz General input 2 x 63 A/2P UPS input 63 A/1P Battery power distribution 125 A/2P x 2 Air conditioner power distribution 25 A/1P MCB x 2...
  • Page 35: Cooling System

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Figure 3-4 Lithium battery Table 3-5 Lithium battery technical specifications Item Specifications Capacity 100 Ah Voltage 48 V DC Application scope 6 kVA UPS Dimensions (H x W x D)
  • Page 36: Technical Specifications

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Item Split-Type Air Conditioner Indoor unit operating 5%–95% RH (non-condensing) humidity Storage temperature –40°C to +70°C (without refrigerant) –40°C to +55°C (with refrigerant) Storage humidity 5%–95% RH (non-condensing) Altitude 0–4000 m (derated when the altitude ranges...
  • Page 37: Management System

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Item Split-Type Air Conditioner a: The cooling capacity is obtained when the indoor dry bulb temperature is 37°C, the indoor wet bulb temperature is 24°C, and the outdoor dry bulb temperature is 35°C.
  • Page 38: Monitoring

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture 3.4.2.1 Monitoring ● Temperature and humidity monitoring: Detects and collects statistics on the ambient temperature and humidity inside the smart module. ● Water leakage monitoring: Detects water leakage at the bottom of the smart module and provides real-time alarm signals.
  • Page 39: Historical Data Query

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture ● Alarms can be classified into four severities: critical, major, minor, and warning. The alarm severities can be user-defined. ● Active alarms can be filtered by device and alarm severity.
  • Page 40 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Figure 3-6 ECC800-Pro (1) Power module (2) Main control module Table 3-9 ECC800-Pro environmental specifications Item Specifications Operating –20°C to +50°C temperature Storage temperature –40°C to +70°C Relative humidity 5%–95% RH (non-condensing) Altitude 0–4000 m (When the altitude is between 3000 m and...
  • Page 41: Main Control Module

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Figure 3-7 ECC800-Pro (rear view) (1) 53.5V DC_OUT1 (2) 53.5V DC_OUT2 (3) AC_INPUT1 (4) AC_INPUT2 Power Port The ECC800-Pro provides four power ports, including two AC input ports (AC_INPUT1 and AC_INPUT2) and two DC output ports (DC_OUTPUT1 and DC_OUTPUT2).
  • Page 42 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture (5) COM1/AIDI_4 (6) COM3/12V (7) WAN1 (8) LAN1/POE (9) LAN2/POE (10) WAN2 (11) COM4/CAN (12) COM2/AIDI_5 (13) AIDI_3 (14) DO/12V (15) RF_Z (802.15.4) (16) WLAN (reserved) (17) 4G (18) SW button...
  • Page 43 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Item Specifications LAN port ● Supports two LAN ports, which can be connected to the LAN. The ports support autonegotiation of 10/100/1000 Mbit/s communication rates. ● Connect shielded network cables to the LAN ports.
  • Page 44 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Item Specifications Supports the 4G module, SMS sending, and 3G communication, and provides a standard SIM card slot. 1. China: 2G and 4G networks support China Unicom or China Mobile SIM cards, and 3G networks support only China Unicom SIM cards.
  • Page 45 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Table 3-14 ECC800-Pro 4G parameters Item Specifications 3G/4G operation LTE (FDD): BAND1, BAND2, BAND3, BAND4, BAND5, frequency BAND7, BAND8, BAND20 DC-HSPA+/HSPA+/HSPA/UMTS: 850/900/1900/2100 GSM/GPRS/EDGE: 850/900/1800/1900 MHz 3G/4G EIRP (max.) 23 dBm Communications Port The ECC800-Pro provides the following communications ports.
  • Page 46 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Item Description Yellow ACT data communication, blinking indicator Table 3-16 COM1/AIDI_4, COM2/AIDI_5 port pin definitions Item Description Pin1 RS485+ sequence Pin2 RS485- Pin3 12V DC_OUT Pin4 RS485+ Pin5 RS485- Pin6...
  • Page 47 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Table 3-18 COM4/CAN port pin definitions Item Description Pin1 RS485+ sequence Pin2 RS485- Pin3 Pin4 RS485+ Pin5 RS485- Pin6 Pin7 CAN_H Pin8 CAN_L The following provides the AIDI_1, AIDI_2 and AIDI_3 ports pin definitions.
  • Page 48 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Table 3-20 DO/12V port pin definitions Item Description Pin1 sequence Pin2 Pin3 12V DC_OUT Pin4 Pin5 Pin6 DO_OUT+ Pin7 DO_OUT- Pin8 Indicator Green Power output indicator indicator ● Steady on: The 12 V DC output is normal.
  • Page 49 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Indica Color Name Status Description Blinking at The software runs properly long (the indicator blinks at 0.5 intervals Hz, on for 1s and then off for 1s) or the ECC800-Pro registers with the NetEco successfully.
  • Page 50: Power Module

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Function Operation Description Indicator Status Description Press and hold down the button for The RF_Z indicator is more than 8s to clear network steady on. parameters. WLAN enabling Press the button for less than 3s to None enable WLAN.
  • Page 51: Environment Monitoring System

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Indicator Color Name Status Description Slight current imbalance Output overvoltage Hibernation The converter generates no protection alarms. Blinking at The communication between long the converter and the outside is intervals interrupted (the indicator blinks at 0.5 Hz, on for 1s and then...
  • Page 52: Electrode Water Sensor

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Figure 3-11 WLDS900 water sensor (1) Water detector (2) Conversion cable end A, connected to (3) Conversion cable the water detector (4) Conversion cable (5) Water detection cable end A,...
  • Page 53: T/H Sensor

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Figure 3-12 Electrode water sensor Table 3-26 Technical specifications of the electrode water sensor Item Specification Operating –40°C to +80°C temperature Storage –40°C to +80°C temperature 3.4.3.2.3 T/H Sensor Figure 3-13 Appearance The T/H sensor uses an RJ45 connector.
  • Page 54: Smoke Detector

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Table 3-27 RJ45 port pin definitions Description Pin1 or Pin 4 Pin2 or Pin 5 Pin3 Pin6 Pin7 Reserved Table 3-28 T/H sensor specifications Item Specifications Temperature measuring range –20°C to +70°C Temperature accuracy ±1°C...
  • Page 55: Video Management System

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Table 3-29 Smoke detector technical specifications Item Specifications Operating voltage 9–27 V Alarm current < 20 mA Indication Monitoring: The red indicator blinks once every 3 to 8 seconds. Alarm reporting: The red indicator is steady on.
  • Page 56: Optional) Ivs1800

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Item Specifications Wide dynamic range 120 dB Focal length 2.8–12 mm Video compression H.265/H.264/MJPEG standard Maximum resolution 1920x1080 Power supply 12 V DC, PoE IP rating IP67 Vandal resistant rating IK10 3.4.3.3.2 (Optional) IVS1800...
  • Page 57 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Category Item IVS1800-C08-04T IVS1800-C08-04T (64CH) (16CH) Platform 16 cameras to one 64 cameras to one IVS1800 performa cameras IVS1800 connect Table 3-32 Hardware specifications Category Item Specifications Storage Hard disk...
  • Page 58: Optional) Vcn510

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Category Item Specifications Dimensions 86 mm x 442 mm x 467 mm (H x W x 3.4.3.3.3 (Optional) VCN510 Figure 3-18 Appearance Table 3-33 Performance specifications Item Specifications Device access and video storage...
  • Page 59: Cabinet Electronic Clasp Lock

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Item Specifications CPU type and maximum number of 1 x ARM Cortex A17 Quad-core @Max. supported CPUs 1.4 GHz Memory capacity 1 GB Network port Two GE network ports Power parameters ●...
  • Page 60 FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Table 3-35 RJ45 port definitions Pin Description Description RS485+ RS485+ RS485- RS485- +12 V power supply +12VDC RS485+ RS485+ RS485- RS485- Ground Table 3-36 LED indicator status Indi Color Name...
  • Page 61: Pad

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Indi Color Name Operat Status Description cato The system is normal. 3.4.3.5 PAD The pad allows the wireless access from the data center management system. You can monitor the equipment in the data center and environmental parameters in real time over the app.
  • Page 62: Optional) Wifi Module

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Item Specifications Button/Port ● Touch button + power switch and volume button ● 3.5 mm stereo headphones port ● Micro SD card port ● MicroUSB port Camera ● Rear camera: 8-megapixel, F2.4 aperture, automatic focus ●...
  • Page 63: Optional) Neteco Intelligent Data Center Management System

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Table 3-39 Technical specifications Item Specifications Wireless IEEE 802.11n, IEEE 802.11g, and IEEE 802.11b standard Network ● 11n: up to 150 Mbps bandwidth ● 11g: up to 54 Mbps ● 11b: up to 11 Mbps Frequency band 2.4–2.4835 GHz...
  • Page 64: Server

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture ● Environment equipment: water sensor, temperature and humidity sensor, and so on ● Video equipment: camera, and so on ● Access control equipment: A standard access management system is integrated to manage and monitor key information such as door status, card swiping, and permission setting.
  • Page 65: Surge Protection And Grounding System

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture Table 3-41 LAN switch Model Maximum Number of Ports S5331-H24P4XC Twenty-four 10/100/1000BASE-T Ethernet ports, four 10GE SFP+ ports S5731-H24P4XC Twenty-four 10/100/1000BASE-T Ethernet ports, four 10GE SFP+ ports 3.5 Surge Protection and Grounding System 3.5.1 Surge Protection Solution...
  • Page 66: Cable Management

    FusionModule500 Smart Mini Data Center User Manual 3 System Architecture ● Connect equipotential cables to metal components without carrying currents in the module, such as metal doors and windows. Each equipotential cable has a minimum cross-sectional area of 6 mm 3.6 Cable Management...
  • Page 67: Installation Guide

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Installation Guide 4.1 Installation Preparations 4.1.1 Tools and Instruments Prepare the tools and meters required for installation. Table 4-1 General tools and instruments Name, Specifications, and Appearance Protective gloves Marker...
  • Page 68 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Name, Specifications, and Appearance Right angle Electrician's knife Impact tool Heat gun Needle-nose Diagonal pliers RJ11 crimping tool Polyvinyl pliers chloride (PVC) insulation tape Wire stripper Hydraulic pliers Wire clippers...
  • Page 69 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Table 4-2 Tools and instruments for installing smart cooling products Name, Specifications, and Appearance Flashlight Hacksaw Pallet truck Electric balance Antifreeze gloves Cutter Welding torch 5% silver solder Oxygen Acetylene...
  • Page 70: Installation Environment Check

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Name, Specifications, and Appearance a. Pressure gauge and leather hose: dedicated for R410A. The measuring range of the pressure gauges must be at least 4.0 MPa, and the leather hoses must withstand a pressure of at least 4.5 MPa.
  • Page 71: Site Equipment Preparation

    Connects to external water pipes to supply water to the humidifier. NO TE If any of the requirements is not met, contact Huawei technical support. 4.1.3 Site Equipment Preparation ● All cabinets and devices have been delivered to the site and checked against the delivery list.
  • Page 72: Installation Scenarios

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide 4.1.4 Installation Scenarios Cabinet Scenario Figure 4-1 Component layout in the cabinet scenario Table 4-4 Components in the cabinet scenario Component Onsite Installation Onsite Cable Connection ECC800-Pro Not required Not required...
  • Page 73: Personnel Requirements

    Only trained and qualified personnel who fully understand basic safety precautions are allowed to install and operate a modular data center. CA UTION Huawei will not be liable for any consequence caused by the violation of this document. The requirements are as follows: ●...
  • Page 74 Check against the packing list that the equipment and fittings are correct and complete. If some fittings are missing or do not comply with the packing list, record the information and contact your local Huawei office immediately. After checking that the cabinet is intact, remove the screw assemblies that...
  • Page 75: Optional) Removing The Aisle Containment

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-2 Removing an ordinary cabinet Remove the cabinet from the pallet and move the cabinet to the installation position. NO TICE To avoid personal injury, prevent the cabinet from falling over during transportation.
  • Page 76 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide NO TICE The cabinet front door is made of glass. Pay attention to the following during transportation: ● Move the cabinet with caution. ● Ensure that the glass door does not collide with sharp objects.
  • Page 77 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Step 3 Loosen the gas spring nuts using an adjustable wrench and remove the gas springs. Figure 4-4 Removing the gas springs Step 4 Disconnect the cabinet ground cable. Step 5 Lift the cabinet doors off the hinges. Remove the front and rear doors.
  • Page 78 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-5 Removing the cabinet doors Step 6 Remove the top plate from the cabinet using a Phillips screwdriver. Figure 4-6 Removing the top plate Step 7 Remove the screws securing the aisle containment to the cabinet using a Phillips screwdriver, and remove the aisle containment from the cabinet.
  • Page 79: Installing A Cabinet

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-7 Removing an aisle containment Step 8 Move the removed glass doors, gas springs, top plate, aisle containment, and cabinet to the specified installation position using an elevator. Step 9 Assemble the removed components with the cabinets by referring to...
  • Page 80 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Procedure Step 1 Determine the cabinet position based on the engineering layout diagram. Step 2 Place the cabinet at the correct installation position. Step 3 Level the cabinet using a wrench.
  • Page 81: Installing A Smart Cooling Product

    4.2.4.1 Materials (Optional) Refrigerant R410A NO TICE Do not use unqualified refrigerant. Huawei will not be liable for any equipment damage caused by unqualified refrigerant. Customers can purchase this material from Huawei or other vendors. Verify that the refrigerant is authentic in the following ways: Refrigerant from name brands such as DuPont, Daikin, and Honeywell is recommended.
  • Page 82 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-9. Find the saturation pressure corresponding to the measured outer surface temperature from Table 4-5. If the deviation between the saturation pressure and the measured internal pressure is greater than 0.2 MPa, the refrigerant does not meet the requirements, and needs to be replaced.
  • Page 83 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Saturation Gauge Saturation Gauge Saturation Gauge Temperatu Pressure Temperatu Pressure Temperatu Pressure re (°C) (MPa) re (°C) (MPa) re (°C) (MPa) 1.19 2.04 3.26 1.23 3.34 1.27 2.15 NO TE 1 MPa ≈...
  • Page 84 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Item Specifications Liquid pipe 2/9 inch (6 mm), pressure withstanding capacity ≥ 4.5 MPa Thermal insulation foam ≥ 13 mm Water Pipe Drainpipes are hoses that extend 1 m out of the smart cooling product.
  • Page 85: Layout Principles

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Cable NO TICE ● The site ground resistance must be less than 0.1 ohm. ● The cable fire resistance rating must be at least VB. Table 4-8 Cable specifications Application Scenario...
  • Page 86: Installing An Indoor Unit

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-12 Layout for the scenario where the outdoor unit is placed higher than the indoor unit Figure 4-13 Layout for the scenario where the indoor unit is placed higher than the outdoor unit 4.2.4.3 Installing an Indoor Unit...
  • Page 87: Exhausting Nitrogen From An Indoor Unit

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-14 Installing an indoor unit NO TE ● Remove the desiccant bound to the front panel of the smart cooling product before installation. ● The indoor unit of the smart cooling product does not have an external indicator. The main control board inside the indoor unit has an indicator, which can be seen only after the rear panel is opened.
  • Page 88 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-15 Stop valve (1) Needle valve nut (2) Rear cover nut (3) Black plastic nut Procedure Step 1 Open the stop valve on the gas pipe of the indoor unit using a 5 mm hex key.
  • Page 89: Installing An Outdoor Unit

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide NO TICE There should be a great sound of airflow during the exhausting. Figure 4-17 Exhausting nitrogen from an indoor unit (1) Pressure gauge (2) Gas pipe needle valve (3) Liquid pipe needle valve NO TE When exhausting nitrogen, do not remove the valve plug in case of losing it.
  • Page 90: Securing An Outdoor Unit

    ● If the site installation environment is complicated and the preceding conditions are not met, contact Huawei technical support. Space Requirements Figure 4-18 Space requirements 4.2.4.5.2 Securing an Outdoor Unit Prerequisites ●...
  • Page 91: Installing A Low-Temperature Component

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Context NO TICE ● Move the outdoor unit close to the installation position before unpacking. You are advised to keep the outdoor unit vertical during transportation. If tilt is not avoidable, the tilt angle cannot exceed 15°.
  • Page 92 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Procedure Step 1 Place the low-temperature component in an open indoor area. Figure 4-20 Appearance of a low-temperature component Figure 4-21 Interior of a low-temperature component Step 2 Connect pipes. The low-temperature component has no dedicated wiring terminal and uses the 5 m power cable delivered with it.
  • Page 93: Connecting Pipes

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide NO TICE The liquid inlet pipe and liquid outlet pipe of the low-temperature component are φ12.7 mm copper pipes. – If φ12.7 mm liquid pipes are required, no expansion or shrinkage is required for connecting the low-temperature component.
  • Page 94 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Pipe Length NO TICE Lay out pipes based on site requirements and the following principles: ● The length of a pipe should be as short as possible. The recommended length is within 10 m.
  • Page 95 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Connection Procedure WARNING ● Release nitrogen from the indoor unit before connecting it. ● Prepare copper pipes for connecting indoor and outdoor units. Ensure that the copper pipes are clean, free from impurities and moisture.
  • Page 96 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide When the direction of the refrigerant pipe is changed, add a support at the position that is 1000 mm away from the changing point. When the refrigerant pipe is straight, add a support every 2500 mm.
  • Page 97 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-25 Top piping scenario Figure 4-26 Bottom piping scenario Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 98: Injecting Nitrogen To Preserve Pressure

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Step 5 If a low-temperature component is configured, connect the pipe to the low- temperature component. NO TE Top or bottom piping does not affect the installation of the low-temperature component.
  • Page 99 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Procedure Step 1 Open the stop valve for the gas pipe of the indoor unit. NO TICE Before opening the indoor unit stop valve, ensure that the stop valve on the gas pipe of the outdoor unit is closed.
  • Page 100: Connecting Water Pipes

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Result After the copper pipes of the low-temperature component are connected (the stop valve of the indoor unit should be open), inject nitrogen through the upstream and downstream needle valves of the expansion valve to 3.5 MPa and preserve the pressure for 24 hours.
  • Page 101 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide NO TICE ● A φ22 mm automatic drainpipe cannot be routed from the top. A φ6 mm forcible drainpipe is used. The lift of the forcible drainage pump is 5 m.
  • Page 102 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-32 Connecting a drainpipe Step 2 Route the drainpipe from the bottom. NO TICE ● The smart cooling product fitting bag contains drainpipe connectors. Use hoses or rigid pipes based on the site requirements.
  • Page 103: Connecting Cables

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Install the drainpipe. Figure 4-34 Drainpipe routed from the bottom NO TICE After routing a water pipe, secure it to the pipe assembly using cable ties, and seal the cable hole using firestop putty.
  • Page 104 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-35 Electrical ports on the indoor unit (1) Main power ports (2) Outdoor unit power ports (3) Debugging port (4) Communications port (5) Teamwork control CAN port (6) T/H sensor port Figure 4-36 shows the cable connections to the smart cooling product.
  • Page 105 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-36 Cable connections to the smart cooling product Figure 4-37 Cable route between indoor and outdoor units Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 106 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide NO TICE ● To ensure personal safety, ensure that the metal shell of the smart cooling product is properly connected to the ground electrode after installing the product. Ground the smart cooling product properly during installation.
  • Page 107: Vacuumization

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide 4.2.4.11 Vacuumization Prerequisites ● All pipe connectors are correct, and the refrigerant pipe tilts and has supports. ● All pipes have been checked for leakage, and all pipes are not bent by a large angle.
  • Page 108 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Procedure Step 1 Connect a pressure gauge to the gas pipe needle valve (low pressure, thick pipe) and liquid pipe needle valve (high pressure, thin pipe) of the indoor unit, and connect a vacuum pump.
  • Page 109 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Step 7 After ensuring that the pressure does not rise, open the stop valves for the gas pipe and liquid pipe of the outdoor unit. NO TICE ● After the outdoor unit stop valves are opened, the refrigerant in the outdoor unit flows to the engineering pipe and indoor unit pipe.
  • Page 110: Installing Power Supply And Distribution Devices

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide product is started, refrigerant must be sucked from the needle valve after the expansion valve. The refrigerant cylinder should be upside down or tilted (more than 45°). Ensure that the refrigerant is slowly sucked into the compressor, preventing the compressor from being damaged due to slugging.
  • Page 111: Optional) Installing Busbars

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-41 Installing a lithium battery NO TICE ● The lithium battery weighs about 43 kg. Check the load-bearing capability of the rack tray before installation. ● The lithium battery is 396 mm deep. Check the depth of the rack before installation.
  • Page 112: Installing Pdu2000S

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Procedure Step 1 Install busbars. Open the cabinet rear door. Install floating nuts at the busbar installation position. Secure the busbar to the installation position using screws. NO TE The busbar is installed 2 U above the last lithium battery. Determine the busbar installation position based on the lithium battery configuration.
  • Page 113: Installing Monitoring Devices

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-43 Installing PDU2000s ----End 4.2.6 Installing Monitoring Devices 4.2.6.1 Installing the SIM Card and Antenna If a subscriber identity module (SIM) card and an antenna are configured, perform the following steps to install them.
  • Page 114 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-44 Removing the ECC800-Pro main control module Figure 4-45 Installing a SIM card Step 3 Reconnect the signal cable to the panel of the ECC800-Pro main control module based on the recorded position.
  • Page 115: Installing A Pad

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-46 Antenna cable routing Connect the antenna cable to the antenna port on the ECC800-Pro. Figure 4-47 Installing an antenna cable ----End 4.2.6.2 Installing a PAD Context The PAD is to be installed on the front door of the cabinet.
  • Page 116 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-48 PAD installation position (1) PAD installation position Procedure Step 1 Adjust the width and height of the PAD support to match the dimensions of the PAD to be installed.
  • Page 117 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-49 Adjusting screws (1) Adjustment screws Step 2 Remove nuts from the PAD support, insert the support into the mounting holes on the cabinet front door, and reinstall the nuts to secure the support to the front door.
  • Page 118: Installing A Remote T/H Sensor For The Smart Cooling Product

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide NO TICE Ensure that the PAD is installed securely and reliably. Figure 4-51 Installing a PAD Step 5 Connect the cable from the USB port on the ECC800-Pro to the charging port on the PAD.
  • Page 119: Installing T/H Sensors

    4 Installation Guide Table 4-12 DIP switch settings on T/H sensors Address DIP Switch Sequence No. NO TICE The default address of T/H sensors purchased from Huawei is 1. ----End 4.2.6.4 Installing T/H Sensors Procedure Step 1 Install T/H sensors.
  • Page 120: Routing The Cable To A Wlds900 Water Sensor

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide 4.2.6.5 Routing the Cable to a WLDS900 Water Sensor If the water sensor is required, perform the following steps to install it. Context ● The water sensor is composed of the water detection cable (BOM number: 33010445), water detector (BOM number: 33010352), and conversion cable (packed with the water detector).
  • Page 121 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Procedure Step 1 Figure 4-53 shows how to connect the water detection cable to the conversion cable. Figure 4-53 Connecting cables (1) Conversion cable end B, connected to the (2) Water detection cable end A, connected to...
  • Page 122: Installing An Electrode Water Sensor

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-55 Installing fasteners NO TICE When laying out the water detection cable, ensure that the water detector is close to the cabinet to facilitate further cable connections. Step 6 Place the water detection cable onto the fastener, secure the fastener, and keep...
  • Page 123: Optional) Installing A Server

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-57 Signal cable routing ----End 4.2.6.7 (Optional) Installing a Server Procedure Step 1 Determine the installation position of the server and check whether floating nuts are installed. If not, install them first.
  • Page 124 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-59 Installing guide rails Place a guide rail horizontally at the installation position in the cabinet. Tighten the screws to secure the guide rail. Repeat the preceding steps to install the other guide rail.
  • Page 125: Optional) Installing A Camera

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-61 Connecting the power cable Use a hook-and-loop fastener to secure the power cable. Figure 4-62 Securing the power cable Route the power cable along the cable tray neatly, use cable ties to bind the power cable, and use diagonal pliers to trim off the excess of the cable ties.
  • Page 126 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Preparations Tool: Phillips screwdriver Materials: SD card, camera Procedure Step 1 Install an SD card. Remove the transparent cover using a Phillips screwdriver. Figure 4-63 Removing the transparent cover Gently insert the SD card into the SD card slot.
  • Page 127 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-64 Installing an SD card Step 2 Route the camera cable through the top of the cabinet. Step 3 Align the mounting holes in the camera base with those in the mounting plate, and screw the camera to the mounting plate.
  • Page 128 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-66 Installing the camera mounting plate Step 5 Use a Phillips screwdriver to loosen the screws on both sides of the lens, adjust the surveillance angle, and tighten the screws to 0.6 N·m.
  • Page 129: Optional) Installing A Lan Switch

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide NO TE The camera features a three-axis design. The camera can be adjusted by –175° to +180° horizontally, and the lens can rotate –175° to +180° and be adjusted by 0° to 65° vertically.
  • Page 130: Optional) Installing A Vcn510

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-69 Installing a LAN switch Step 3 Connect the LAN switch power cable to the PDU2000. Step 4 Connect a port on the LAN switch to the WAN1 port on the ECC800-Pro using a network cable.
  • Page 131 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Procedure Step 1 Install a hard disk. Use a Phillips screwdriver to loosen three fastening screws (M3 x 6 countersunk screw, black) on the left and right of the subrack covers shown in the lower-left figure.
  • Page 132 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-73 Removing the upper cover of the chassis NO TE When removing the upper cover from the chassis, do not use one hand to perform this operation. Otherwise, the upper cover may collide with the components inside the device, bringing risks of component damages.
  • Page 133 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-75 Installing the SATA cable and power cable (1) SATA cable (2) Power cable NO TE When the VCN510 is delivered, the SATA cable connecting to the hard disk is fixed using blue tapes.
  • Page 134 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-77 Installing a hard disk Hold the disk with one hand. Use the other hand to turn over the device at a 90-degree angle. Fasten the preinstalled screws from the rear panel of the device.
  • Page 135 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-79 Installing the floating nuts (1) Floating nuts NO TE The VCN510 is compact and lightweight. It can be directly fixed on the cabinet with M6 screws and mounting ears without using a guide rail. If a guide rail has been installed in the cabinet, you are advised to remove the guide rail first and then install the device in the cabinet.
  • Page 136: Optional) Installing An Ivs1800

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Phillips screwdriver to fix the M6 screws on the mounting ears. Each mounting ear uses two M6 screws. Figure 4-81 Installing the device ----End 4.2.6.11 (Optional) Installing an IVS1800 Context By default, the IVS1800 is delivered without disks.
  • Page 137 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Place the hard disks with ports facing upwards and align the screw holes on the hard disk tray with the hard disks and fasten the screws. Before the installation, ensure that the fastener of the hard disk tray is on a different side from the hard disk port, as shown in the lower left figure.
  • Page 138 If the vents are blocked, change the guide rails. ● Huawei provides guide rails that can be adjusted from 500 mm to 800 mm for additional purchase if required for IVS1800 installation.
  • Page 139 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-88 Installing a cage nut Install guide rails. Horizontally place a guide rail to the installation location through the positioning block at the front of the guide rail and the positioning hook at the rear of the guide rail.
  • Page 140 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-90 Installing a filler panel for guide rails Install the cage nuts that secure the IVS1800. The cage nut installation locations are the first and sixth holes along the guide rails, as shown in the following figure.
  • Page 141: Cable Routing

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-92 Installing mounting ears Install the IVS1800 in the cabinet. 1. Lift the device from both sides and carefully position it at the front of the cabinet. 2. Lift the device slightly above the guide rails, gently place it on the guide rails, and then slide it into the cabinet until the mounting ears of the subrack contact the mounting bars at the front of the cabinet.
  • Page 142: System Cabling Rules

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide 4.3.1 System Cabling Rules Attaching Cable Labels NO TICE A cable label must be consistent with the corresponding cabinet number. Find the corresponding cable based on the wiring diagram in the cable fitting bag, and attach the corresponding cable label taken out from the cable fitting bag to both ends of the cable by wrapping the ends.
  • Page 143 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-95 Cable organizer Route and lay out a large number of cables in different areas to ensure neat cabling and facilitate cable search and maintenance. Route several flat cables along the same path and then overlap them as one.
  • Page 144 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-97 Cable connection positions Before installing a semi-flexible cable, use a dedicated tool to curve the cable. Do not curve the cable while holding the cable connector by hand.
  • Page 145 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide After binding cables, cut off the excess parts of cable ties and trim away any burrs, as shown in Figure 4-99. Figure 4-99 Cutting off the excess part of a cable tie Do not use cable ties at a place where the cables are bent.
  • Page 146: Grounding The Smart Module

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide 4.3.2 Grounding the Smart Module Connect the ground point in the cabinet to the general ground bar. Connect the general ground bar in the cabinet to the floor ground bar or collective ground bar.
  • Page 147: Cable Routing Description

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide 4.3.3.1.1 Cable Routing Description Figure 4-103 Holes for routing cables through the top of the cabinet (1) Holes for pipes of smart (2) Signal cable holes (3) Input power cable holes...
  • Page 148: Connecting Cabinet Input Power Cables

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-105 Position for binding cables routed across the cabinet interior (1) Position for binding cables routed across the cabinet interior 4.3.3.1.2 Connecting Cabinet Input Power Cables Context The power distribution subrack position in the cable connection description is for reference only.
  • Page 149: Bottom Cable Routing

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-106 Connecting input power cables to the PDU ----End 4.3.3.2 Bottom Cable Routing Cables connect to the same positions on the power distribution subrack irrespective of whether cables are routed through the top or bottom of the cabinet, but the cable routes inside the cabinet are different.
  • Page 150 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-107 Holes for routing cables through the bottom of the cabinet (1) Smart cooling product water inlet pipe and (2) Hole for the signal cable and water sensor drainpipe holes...
  • Page 151: Connecting Pdu2000 Power Cables

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-108 Cable route example in the bottom cable routing scenario 4.3.3.3 Connecting PDU2000 Power Cables Context If the PDU2000 is not configured with industrial connectors, connect the PDU2000 cables.
  • Page 152 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-109 Connecting PDU2000 cables Step 2 Take out the PDU2000 cables and connect the cord end terminals of the power cables to the PDU2000 wiring ports, as shown in Figure 4-110.
  • Page 153: Connecting Cables Between The Lithium Battery And The Ups

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Follow-up Procedure Before connecting the power plug of a device to the PDU2000, loosen the locking device on the PDU2000. After connecting the power plug, tighten the locking device. 4.3.3.4 Connecting Cables Between the Lithium Battery and the UPS Context ●...
  • Page 154 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-112 Connecting cables between the busbars, PDU, and UPS Step 2 Connect communications cables between lithium batteries and the UPS. After lithium batteries are connected in parallel, connect a signal cable to the BMS port of the UPS.
  • Page 155: Management System Cable Connection

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-113 Connecting communications cables between lithium batteries and the UPS ----End 4.3.4 Management System Cable Connection 4.3.4.1 Connecting Cabinet Electronic Clasp Lock Cables Prerequisites The cabinet electronic clasp locks have been installed.
  • Page 156: Connecting Cabinet T/H Sensor Cables

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-114 Connecting cabinet electronic clasp lock cables ----End 4.3.4.2 Connecting Cabinet T/H Sensor Cables Prerequisites The required cables have been prepared. Procedure Step 1 Connect the OUT port on the T/H sensor on the front door to the RS485_IN port on the T/H sensor on the rear door in series.
  • Page 157: Connecting Vcn Cables

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-115 T/H sensor cable route ----End 4.3.4.3 Connecting VCN Cables Prerequisites Cables have been prepared. Procedure Step 1 Connect one end of the ground cable to the ground terminal on the device and the other end to the ground point on the cabinet.
  • Page 158: Connecting Ivs1800 Cables

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Step 2 Connect one end of the network cable to any GE network port on the VCN. Figure 4-116 Ports on the VCN (1) Ground terminal (2) GE1 port (3) GE2 port...
  • Page 159: Connecting A Cable To The Wlds900 Water Sensor

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Step 3 Connect one end of the power cable to the input power port on the power module and the other end to the PDU2000 in the cabinet. NO TE After connecting the power cable, turn on the power switch on the panel to start the device.
  • Page 160: Verifying The Installation

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide 4.4 Verifying the Installation Cabinet Installation Check Table 4-15 Cabinet installation check items Check That Check Result The cabinet position is consistent with the □ Passed □ Failed equipment room layout diagram.
  • Page 161 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Check That Check Result The flat washers and spring washers of all wiring □ Passed □ Failed terminals are securely installed. Cables are bound neatly and cable ties are □ Passed □ Failed secured evenly and properly.
  • Page 162 FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Check That Check Result Lithium battery terminals are upright and free □ Passed □ Failed from damage, break, and acid leakage. Lithium battery cables are connected correctly. □ Passed □ Failed DIP switches on devices are correctly set.
  • Page 163: Power-On Commissioning

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Power-On Commissioning 5.1 Power-On Commissioning for the Power Supply and Distribution System Prerequisites The installation has been checked. NO TICE Configure an upstream protective device that meets the overload and short-circuit protection requirements for the cabinet.
  • Page 164: Ups Power-On Commissioning

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning NO TICE When switching on the circuit breakers, observe whether there is any abnormal phenomenon, such as sparks. ----End 5.1.1 UPS Power-On Commissioning Step 1 Switch on the external battery circuit breaker (if any).
  • Page 165: Connecting The Lithium Battery Supply

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Battery Capacity Description ● Default value: 100 Ah ● Value range: 50–2400 Ah. The value increases by 50 Ah each time you press SELECT. Step 5 Press and hold ON/MUTE for more than 5s. Release the button when you hear a beep sound.
  • Page 166: Powering On Devices

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning 5.2.1 Powering on Devices Prerequisites ● Check that the humidifier water inlet pipe and drainpipe are correctly connected, that the thermal insulation foam is intact, and that refrigerant has been charged.
  • Page 167 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Log in to the ECC800-Pro WebUI as an administrator. Add a rack-mounted HR04A. Table 5-1 Adding a smart cooling product (rack-mounted HR04A) Path Parameter Setting Choose Device Select Air Conditioner from the drop-...
  • Page 168: Commissioning The Cooling System

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning CA UTION After the smart cooling product is shut down, the temperature of the smart module increases and data running is affected. Exercise caution when performing this operation. ----End 5.2.3 Commissioning the Cooling System Prerequisites Check that the indoor and outdoor units have been powered on.
  • Page 169 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Table 5-3 Amount of refrigerant to be added Liquid Pipe Diameter (mm) Amount of Refrigerant to Be Added (kg/m) 0.009 9.52 0.04 12.7 High-quality refrigerant R410A is recommended. CA UTION Wear antifreeze gloves when performing refrigerant related operations.
  • Page 170 Tighten the needle valve nut when the charge is complete. Check whether a needle valve leaks by applying soapy water to the valve vent or using a halogen leak detector. If it leaks, contact Huawei technical support. Issue 02 (2020-12-25)
  • Page 171: Management System Power-On Commissioning

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-3 Charging refrigerant (1) Refrigerant cylinder (2) Electronic balance (3) Pressure gauge (4) Connection nut (5) Gas pipe needle valve (6) Liquid pipe needle valve ----End Exception Handling Step 1 Check that the T/H control mode and T/H set point are properly set.
  • Page 172 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Table 5-4 Default IP addresses for the WAN and LAN ports on the ECC800-Pro Port Default IP Address WAN1 192.168.8.10 WAN2 192.168.0.10 192.168.248.10 LAN1 and LAN2 192.168.248.10 NO TICE ● In ECC800 V100R002C10 and earlier versions, the default IP address of port WAN_1 is 192.168.1.10.
  • Page 173 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Compatibility View, and add the web access address to the compatibility view. Choose Tools > Internet options > Security, choose Add the ECC800-Pro IP address to the list of trusted sites.
  • Page 174: Preparations And App Login

    – After the first login, change the password in time to ensure account security and prevent unauthorized network attacks, such as data tampering. Huawei will not be liable for any security issues caused by your failure to change the preset password in time or password loss after changing.
  • Page 175 Save. Install the Huawei AppGallery. If the downloaded file exists in the drop- down list box, tap the file to install the Huawei AppGallery. If the downloaded file does not exist in the drop-down list box, choose File > Local on the desktop, find the Download folder, and click the Huawei AppGallery installation package.
  • Page 176 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning NO TE ● The initial password is Changeme after the WiFi function is enabled. The password is valid only after you hold down the button for the first time to enable the WiFi function.
  • Page 177: Performing Startup Password Authentication

    Record the values of Barcode and Verify Code in the displayed Startup Password dialog box. Within 24 hours, inform Huawei technical support of Barcode and Verify Code to obtain the password. After obtaining the password, enter the password in the Password text box and click Submit to complete the authentication of the startup password.
  • Page 178 Save. Install the Huawei AppGallery. If the downloaded file exists in the drop- down list box, tap the file to install the Huawei AppGallery. If the downloaded file does not exist in the drop-down list box, choose File > Local on the desktop, find the Download folder, and tap the Huawei AppGallery installation package.
  • Page 179: How Can I Set The Date And Time

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning NO TE – After the first login, change the password in time to ensure system access security. – When the mobile phone app connects to the monitoring system, the WiFi function of the monitoring system is disabled by default.
  • Page 180: Creating A Micro-Module Plan View

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-7 Adding a device ----End 5.3.6 Creating a Micro-module Plan View Procedure Step 1 Choose Home > Plan View, create a micro-module in Micro-Module View and set the layout and device quantity based on the actual micro-module scenario.
  • Page 181: Commissioning Sensors

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Path Parameter Setting devices are Communicati Select COM4 from the drop-down list box. displayed. ons Port NOTE The setting example indicates that the UPS2000G is connected to the COM4 port on the ECC800-Pro.
  • Page 182: Commissioning A T/H Sensor

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Step 2 Check the monitoring functions of smoke detector. Table 5-6 Commissioning the detector Check Method Normal Connection Status Alarm Clearance Method Simulate a Smoke DI alarm is displayed Disconnect the smoke...
  • Page 183 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Table 5-7 Setting device addresses Address Toggle Toggle Toggle Toggle Toggle Toggle Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 6 Step 2 Add a T/H sensor.
  • Page 184: Commissioning The Wlds900 Water Sensor

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Check Method Normal Connection Status Set T/H sensor alarm Choose Monitoring > Aisle > T/H Sensor Group thresholds. > T/H Sensor n > Running Parameters and set High temperature alarm threshold, Low...
  • Page 185: Commissioning The Electrode Water Sensor

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Set Leak sensor to Enable and click Submit. Confirm that Leak sensor type is automatically identified as Leak sensor(Rope). Step 2 Check the function of the water sensor. Check Method...
  • Page 186: Commissioning A Cabinet Electronic Clasp Lock

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Set Leak sensor to Enable and click Submit. Set Leak sensor type to Leak sensor(Electroc) and click Submit. Step 2 Check functions of water sensors. Table 5-10 Function check Check Method...
  • Page 187 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-9 Toggle switch addresses of the cabinet electronic locks NO TICE The number indicates the DIP switch setting of the electronic clasp lock. Table 5-11 Setting device addresses Address...
  • Page 188 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Click Test Connect to check whether the connection between the cabinet electronic clasp lock and the ECC800-Pro is normal. – If the connection is normal, click Confirm. The connected devices are displayed in the Number of connected devices list.
  • Page 189 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-10 Adjusting the position of a clasp lock Check whether there is interference between the lock tongue and the cabinet column. If so, adjust the installation position of the lock tongue.
  • Page 190: Configuring Event Notification

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-12 Removing the fastener NO TICE If the door still cannot be opened or closed properly, check the following items: ● Whether cables are connected correctly ● Whether the DIP switch setting is correct ----End 5.3.10 Configuring Event Notification...
  • Page 191 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning ● The ECC800-Pro is connected to a network with an email server through a WAN port. Both the Internet and local area network (LAN) are supported. Procedure Step 1 Choose System Settings > Event Notification.
  • Page 192 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Table 5-14 Main parameters on the outbox configuration page Email Email Mailbox Server Encryption Remarks Type Server IP Address Mode and Domain SMTP port Name Sina Mail smtp.sina.co How to obtain: Non- ●...
  • Page 193 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-14 Adding an email address to receive emails NO TE Click Test to check whether the added mailbox is available. If it is available, Successfully to send the test email. is displayed. If it is unavailable, Failed to send the test email. is displayed.
  • Page 194 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-15 Adding a mobile number NO TE Click Test to check whether the added mobile phone number is available. If it is available, Successfully to send the test short message. is displayed. If it is unavailable, Failed to send the test short message.
  • Page 195: Video Management

    Before commissioning a camera, prepare the following documents in addition to this document. Table 5-15 Documentation for commissioning preparation Component Document C3220 Huawei C Series SDC 8.0.1 Product Documentation VCN510 VCN510&VCN520&VCN540 Product Documentation IVS1800 IVS1800 8.1.0 Product Documentation Issue 02 (2020-12-25)
  • Page 196: Networking Scenario

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning 5.3.11.2 Networking Scenario LAN Switch Networking Scenario If there are multiple VCNs or IVS1800s for multiple smart modules, you are advised to evenly distribute the cameras to each VCN or IVS1800.
  • Page 197 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning NO TE You need to set Internet Explorer before accessing the camera WebUI for the first time. Table 5-16 Internet Explorer settings Settings Procedure Disable the proxy server. 1. Choose Tools > Internet Options.
  • Page 198 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Settings Procedure Set Use Pop-up Blocker to Disable. 1. Choose Tools > Internet Options. The Internet Options dialog box is displayed. 2. Click the Security tab. 3. Select Internet. 4. Click Custom level.
  • Page 199 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Table 5-17 IP address parameters Parameter Description IPv4 address Method for obtaining the IP address. The options are assignment Obtain IP address automatically and Use the following IP address. The default value is Obtain IP address automatically.
  • Page 200 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-21 Setting secondary stream 1 parameters Table 5-18 Video stream parameters Parameter Description Primary stream/ Set the stream type based on the site requirements. Secondary – Primary stream: The primary streams feature high stream bit rate, definition, and bandwidth usage.
  • Page 201 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Parameter Description Encoding Set the coding protocol based on the site requirements. protocol The options are as follows: – H.264: The H.264 protocol requires relatively small bandwidth to ensure video quality.
  • Page 202: Commissioning A C3220 Camera (Sd Card Configured)

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Parameter Description Bit rate control This parameter is available only when you set Bit rate mode type to Constant bit rate. The options are as follows: – Frame rate priority: Ensure the smoothness of the video image.
  • Page 203 User Manual 5 Power-On Commissioning Procedure Step 1 Log in to the Huawei camera WebUI. Configure the PC IP address and the camera IP address in the same network segment. Enter the camera IP address (192.168.0.120 by default) in the address bar of the Internet Explorer and press Enter.
  • Page 204 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-23 Setting audio and video parameters NO TE If longer-time video storage is required, set camera parameters according to the following table. Table 5-19 Camera configuration parameters Condition Result...
  • Page 205: Commissioning A Network Video Recorder (Vcn Scenario)

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Choose Settings > Intelligent Analysis > Common Intelligence. Select Enable, click Add, add motion detection areas, set motion detection parameters, and click Save. Set the deployment policy. Figure 5-24 Setting the deployment policy Set the alarm linkage policy.
  • Page 206: Initializing Hard Disks

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning NO TE The OMU portal supports Internet Explorer 8.0 and later versions. Step 2 On the login page, enter the user name admin and preset password Change_Me, and click Log In to enter the OMU portal page. A message is displayed upon the first login indicating that you should change the password.
  • Page 207 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-28 Initializing disks Step 4 Choose whether to create a RAID group. To set disks as a RAID group, select RAID1. To set disks to work independently, select NON-RAID.
  • Page 208 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-29 RAID group status of RAID 1 When two disks are configured, if NON-RAID is selected for the disks, RAID 1 is created for the system partition. Figure 5-30 RAID group status of disks that work independently (two disks) If only one disk is configured, RAID 0 is created for the system partition after disks are initialized.
  • Page 209: Setting Parameters On The Vcn Webui

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning 5.3.11.4.3 Setting Parameters on the VCN WebUI Prerequisites The description and links in this section are for reference only. For detailed Configuration Guide . For details, see the documentation configuration, see the delivered with the device or obtain the documentation by referring to the "Reference Documentation"...
  • Page 210 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning NO TE Currently, the VCN and NTP source server must be in the same LAN for NTP synchronization. For details, see Step If the VCN and the NTP source server are not in the same LAN, you need to manually set the time as follows: Choose Local Configuration >...
  • Page 211 ----End Follow-up Procedure ● (Optional) Set up a VCN stack. For details, log in to the https:// e.huawei.com/, search for the VCN product documentation, open the documentation, and see the section (Optional) Deploying IVS in Stack Mode. ● (Optional) Create a VCN cluster. For details, log in to the https:// e.huawei.com/, search for the VCN product documentation, open the...
  • Page 212: Setting Parameters On The Vcn Ivs Client

    Method 2 1. Log in to the VCN OMU Portal, choose Local Configuration > Basic Configuration, and view Current version. 2. Log in to https://support.huawei.com/enterprise/, and search for Client Package.zip followed by the VCN model (Client Package.zip VCN540 for example). In the search result, click...
  • Page 213 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Click Log In to access the client home page. A message is displayed upon the first login indicating that you should modify the password. After modifying the password, keep it properly.
  • Page 214: Commissioning A Network Video Recorder (Ivs1800 Scenario)

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning NO TE If you set the recording plan policy is to All, you do not need to set the recording plan time. Click Next to complete the recording plan setting. When is displayed in the status bar, the recording plan has been set successfully.
  • Page 215: Setting Parameters On The Ivs1800 Webui

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning 5.3.11.5.1 Setting Parameters on the IVS1800 WebUI Prerequisites For details about the IVS1800 hardware description and installation, see the Quick Start in the corresponding IVS1800 product documentation. For details about the IVS1800 configuration, see the Configuration Guide.
  • Page 216 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Step 3 Configure disk initialization. NO TE Recording data can be stored only after you install and initialize the disks. Choose Local Configuration > Local Disk. In the upper right corner of the RAID Groups area, click Initial Disk Configure disk initialization.
  • Page 217 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning (Optional) Configure the NTP synchronization. After setting The NTP clock source server to Yes, set the IP address of the NTP server. NO TE Currently, the IVS1800 and NTP source server must be in the same LAN for NTP synchronization.
  • Page 218: Setting Parameters On The Iclient

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Step 5 Enable camera NTP synchronization. The camera NTP synchronization function for the server is disabled by default. The camera NTP synchronization function needs to be enabled for the server that connects to the camera.
  • Page 219 Method 2 1. Log in to the OMU portal, choose Local Configuration > Basic Configuration, and view Current version. 2. Log in to https://support.huawei.com/enterprise/, and search for and choose iClient. In the search result, click the Software Download tab, click the version and patch number corresponding to the current version, and download the software package.
  • Page 220 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Figure 5-46 Logging in to the iClient Select Micro Edge Access. Add an IVS1800. Figure 5-47 Adding a device NO TE – If the iClient and IVS1800 are deployed in the same LAN, set Address to the internal IP address of the IVS1800.
  • Page 221 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning On the home page of the iClient, choose System Management > Device Management > Device Management > Micro Edge. Right-click an IVS1800 and choose Camera Access. Select Auto Batch Access and click Start.
  • Page 222: Linkage Control

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning NO TE If there are multiple IVS1800s for multiple smart modules, you are advised to evenly distribute the cameras to each IVS1800. Select the cameras to be added and click Next.
  • Page 223 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Linkage Grouping Table 5-22 Linkage grouping Linkage Default Function Category Status Link Set this linkage status to on: emergency ● If the smart cooling product communicates ventilation properly but does not provide the cooling function,...
  • Page 224: Unlocking The Cabinet Electronic Clasp Lock When A Smoke Alarm Is Generated

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning 5.3.12.1 Unlocking the Cabinet Electronic Clasp Lock When a Smoke Alarm Is Generated Context In this example, the smoke sensor connects to port AI/DI_1. The actual port prevails. Procedure Step 1 Log in to the ECC800-Pro WebUI as an administrator.
  • Page 225: Unlocking The Cabinet Electronic Clasp Lock When A Fire Alarm Is Generated

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning 5.3.12.2 Unlocking the Cabinet Electronic Clasp Lock When a Fire Alarm Is Generated Context In this example, the fire extinguishing system connects to port AI/DI_3. The actual port prevails. Procedure Step 1 Log in to the ECC800-Pro WebUI as an administrator.
  • Page 226: Neteco6000 Management

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning 5.3.13.1 NetEco6000 Management 5.3.13.1.1 Connecting a Communications Cable Procedure Step 1 Connect the communications cable to the WAN1 port on the ECC800-Pro. Figure 5-50 Connecting the communications cable ----End 5.3.13.1.2 Setting NetEco Parameters When the smart module can be connected to the NetEco, perform the following steps to configure parameters.
  • Page 227: Obtaining The Neteco Software License

    5.3.13.1.3 Obtaining the NetEco Software License The NetEco software license is not provided together with software to the customer. Therefore, obtain the NetEco software license in advance. Obtain the license from the Huawei's enterprise support website. ● For enterprise users: Issue 02 (2020-12-25) Copyright ©...
  • Page 228: Powering On A Server

    Data Center > iManager NetEco 6000. Then, apply for the license of the NetEco software by referring to the guide. ● For carrier users: Log in to Huawei's carrier support website https://support.huawei.com. Browse or search iManager NetEco 6000 License Application Guide, iManager NetEco 6000 License Application Guide from Support > obtain Product Support >...
  • Page 229: Loading A Neteco License

    Huawei will not be liable for any security issues caused by your failure to change the preset password in time or password loss after changing.
  • Page 230: Installing The Ne Mediation

    NetEco 6000. Based on the actual NE types and versions to download the mediation software installation package. ● For carrier users: Log into Huawei's carrier support website https://support.huawei.com. Browse or search iManager NetEco 6000 V600R009 Version Mapping, iManager NetEco 6000 V600R009 Version Mapping from Support obtain >...
  • Page 231 Protection Cabinet and Rack Custom under Room ● You can create Container and Container–ShapeNode under ContainerDC. ● You can create Modular, Park, NetecoSite, FusionModule500 and under Subnet. ● You can create DDF, Battery Cabinet, Rack, Modular, Power Cabinet, and Fire Protection Cabinet and Rack Custom under NetecoSite ●...
  • Page 232: Adding A Smart Module

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning NO TE You can adjust the shape of Room, Building–ShapeNode, Floor–ShapeNode, Container–ShapeNode, and NetecoSite. Holding down the Shift key and the left mouse button and then clicking on the corresponding lines can increase the small yellow dot.
  • Page 233 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Step 5 Select the Modular to be added and drag the module icon to the Room area. Figure 5-53 Adding a smart module in the room area Step 6 Modify Management Info of the smart module or retain the default values, and...
  • Page 234 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning If You Then... Need To... Delete You can delete one smart module or multiple smart modules in smart batches on the current page. modules NOTE If a smart module contains subdevices, you cannot delete it. You can delete the smart module only after you delete subdevices in the module.
  • Page 235 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning If You Then... Need To... Figure 5-55 Deleting multiple smart modules in batches Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 236: Creating An Ecc800-Pro On The Neteco

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning If You Then... Need To... 2. Add filter conditions, select multiple smart modules, and click Delete. 3. In the displayed Confirm dialog box, click Yes. Add tools 1. Select the smart module for which you want to add a pillar.
  • Page 237: Cloudopera Neteco Management

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning ● You have created modules in Data Center Planning. Context iManager NetEco 6000 Device Installation and For detailed operations, see Commissioning Guide of the corresponding version. Procedure Choose System > Configuration > Data Center Planning from the main menu.
  • Page 238: Installing The Edcm App

    Huawei will not be liable for any security issues caused by your failure to change the preset password in time or password loss after changing.
  • Page 239: Allowing A User To Log In To The Edcm On A Mobile Device

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning 5.3.13.2.3 Allowing a User to Log in to the EDCM on a Mobile Device Prerequisites You have logged in to the EDCM. Procedure Step 1 Choose System > System Management > User Management.
  • Page 240: Setting Edcm Communication Parameters On The Ecc800-Pro

    Step 2 Open the EDCM app, and enter the Organization, Username, and Password. NO TE ● Organization and Username are the tenant name registered on HUAWEI CLOUD. ● If you fail to log in for three consecutive times, the system automatically displays Verification code.
  • Page 241: Connecting To The Network

    FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Prerequisites ● You have obtained the IP address of the ECC800-Pro as well as the user name and password used for WebUI login. ● You have obtained the IP address of the EDCM server.
  • Page 242 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Procedure Step 1 On the CloudOpera NetEco app, tap in the upper right corner. Step 2 On the Create network screen, enter network information as prompted and tap Confirm. Figure 5-58 Creating a network...
  • Page 243 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Parameter Description Address Address of the network. ----End Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd.
  • Page 244: Routine Maintenance

    FusionModule500 Smart Mini Data Center User Manual 6 O&M O&M 6.1 Routine Maintenance 6.1.1 Monthly Maintenance Table 6-1 Monthly preventive maintenance table Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Power supply and Operating status Check the surge ● The surge ●...
  • Page 245 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Operating ● Ambient ● If the environment temperature: temperature 0–40°C or humidity is abnormal, ● Humidity: check the 0%–95% RH smart (non- cooling...
  • Page 246 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Battery 1. The surface is If the battery appearance clean and tidy appearance is without abnormal, stains. contact Huawei technical 2. The battery support.
  • Page 247 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Indicator The indicator on Check the the power output voltage module is steady and determine green. whether the power module is faulty. If the...
  • Page 248 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Monitor interface Export smart If an alarm is (network cooling product generated, management logs, alarms, handle the system or WebUI) temperature, alarm by...
  • Page 249 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Intelligent lithium Battery No battery Identify the battery management management cause of an monitoring system alarm alarm is alarm based on generated. the alarm information.
  • Page 250: Quarterly Maintenance

    FusionModule500 Smart Mini Data Center User Manual 6 O&M 6.1.2 Quarterly Maintenance Table 6-2 Quarterly preventive maintenance table Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Power supply and Operating status Check the surge ● The surge ● If the surge...
  • Page 251 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Cleanliness Wipe the cabinet Remove the surface using a dust, especially white paper and from the air the paper does filter on the not turn black.
  • Page 252 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Battery 1. The surface is If the battery appearance clean and tidy appearance is without abnormal, stains. contact Huawei technical 2. The battery support.
  • Page 253 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Battery bolts The location of Take photos the signs marked from multiple on battery angles and terminal bolts contact Huawei indicating tight technical connections does support.
  • Page 254 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Shallow discharge Conduct a 1. Locate the test shallow cause when (recommended) discharge test an exception when the UPS is is identified. backed up to 2.
  • Page 255 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Monitoring The monitoring If the indicator module indicator module indicator is off or any is steady green abnormal or blinking condition green. occurs, see 6.2.2...
  • Page 256 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Camera Camera On the ECC800- The monitoring If the availability Pro WebUI, page is properly monitoring choose displayed after page is not Maintenance >...
  • Page 257: Yearly Maintenance

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Water sensor and Functions of the Place the water A water leakage If a water water detection water sensor and detection cable alarm is...
  • Page 258 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Circuit breaker Switch on or off The circuit If the circuit the circuit breaker is breaker cannot breaker after switched on and be switched on...
  • Page 259 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Operating ● Ambient ● If the environment temperature: temperature 0–40°C or humidity is abnormal, ● Humidity: check the 0%–95% RH smart (non- cooling...
  • Page 260 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Power cables and The insulation ● Replace terminals layer of cables is damaged (between the UPS intact and cables. and the power terminals are ●...
  • Page 261 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Battery Check that the Set parameters management settings of correctly. parameter settings battery management parameters meet the requirements in the user manual. Battery bolts...
  • Page 262 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Battery voltage ● Equalized 1. Check charging whether the voltage: 53.5 equalized V DC charging voltage and ● Float float charging charging voltage: 53.4...
  • Page 263 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Capacity test When the UPS is 1. Locate the (recommended) backed up, cause when discharge a an exception battery to the is identified.
  • Page 264 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item ECC800-Pro AC input Input voltage: If the input 200–240 V AC voltage is abnormal, check Frequency: 45– the power grid 55 Hz status and input cable connection.
  • Page 265 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Network interface The green If the indicator indicator indicator is status is steady on, and abnormal, check the yellow the network indicator is cable blinking.
  • Page 266 FusionModule500 Smart Mini Data Center User Manual 6 O&M Maintenance Maintenance Operation Expected Result Troubleshootin Area Item Camera Camera On the ECC800- The monitoring If the availability Pro WebUI, page is properly monitoring choose displayed after page is not Maintenance >...
  • Page 267: Troubleshooting

    UPS again. Otherwise, the fault may be extended, or the UPS may be damaged. ● If the fault is not rectified, contact Huawei technical support. Table 6-4 Power supply and distribution system troubleshooting...
  • Page 268 FusionModule500 Smart Mini Data Center User Manual 6 O&M Symptom Possible Cause Measure The surge protection ● The SPD circuit ● Check that the SPD function fails. breaker is OFF. circuit breaker is turned on. The power ● The SPD ground cable distribution subrack is not connected.
  • Page 269 FusionModule500 Smart Mini Data Center User Manual 6 O&M Symptom Possible Cause Measure The UPS does not start is not pressed long Press for more than after you press enough. 5 seconds until you hear a beep sound. The UPS is overloaded.
  • Page 270: Management System Troubleshooting

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Symptom Possible Cause Measure The user forgot the None ● If the user forgot only password. the LCD password (the preset password is 000001), use the feature code (the preset feature code is 999999) to activate the LCD password.
  • Page 271 FusionModule500 Smart Mini Data Center User Manual 6 O&M Symptom Possible Cause Measure The Alarm indicator Output overvoltage ● If a single PSU is (red) is steady on. protection locked out, disconnect the AC input from the PSU, and then power...
  • Page 272: Alarm References

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Symptom Possible Cause Measure The ALM indicator Faults and alarms are View active alarms on (red) is steady on. generated. the WebUI and clear them one by one. 6.3 Alarm References...
  • Page 273 FusionModule500 Smart Mini Data Center User Manual 6 O&M Component Alarm Name Alarm Possible Cause Measures Severit Inverter fault Critical The inverter output Eliminate the short short-circuits. circuit at the output port cable connection, and then power on and start the inverter again.
  • Page 274: Parts Replacement

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Component Alarm Name Alarm Possible Cause Measures Severit Single Batt. Critical ● The battery shell is ● Check whether the Exception broken, resulting in appearances of electrolyte and abnormal batteries electricity leakage.
  • Page 275: Replacing A Gas Spring

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-1 Removing a cabinet electronic clasp lock Step 4 Install the new cabinet electronic clasp lock at the front or rear door of a cabinet. NO TE ● Before removing a cabinet electronic clasp lock, remember the DIP switch settings on the cabinet electronic clasp lock.
  • Page 276: Replacing A Pdu2000

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Procedure Step 1 Open the front or rear door of the cabinet. Step 2 Remove the nuts from the gas spring using an adjustable wrench. Step 3 Remove the gas springs.
  • Page 277: Replacing Power Supply And Distribution System Components

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Step 2 Switch off the output circuit breaker of the power distribution subrack for the PDU2000. Disconnect the power cables and signal cables from the PDU2000 terminal block. Step 3 Remove the bolts that secure the PDU2000 using a Phillips screwdriver.
  • Page 278 FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-3 Removing the protective panel Step 3 Measure the L1, L2, L3, and N voltages to PE using an electroprobe, as shown in Figure 6-4, and verify that the faulty SPD has no voltage before replacing the faulty surge protection module.
  • Page 279: Replacing A Fuse

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-5 Replacing a surge protection module Step 5 Install the new surge protection module. Step 6 Reinstall the protective panel for the SPD, and switch the SPD circuit breaker to Step 7 Check whether there are alarms on the ECC800-Pro.
  • Page 280: Replacing A Ups2000-G

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-6 Opening the fuse terminal block Step 2 Reinstall the fuse terminal block in the power distribution subrack. Step 3 Close the fuse terminal block. Step 4 Observe the indicator. If the indicator is on, the fuse is functional.
  • Page 281: Replacing A Lithium Battery

    FusionModule500 Smart Mini Data Center User Manual 6 O&M NO TICE Wrap the exposed cable with insulation tape. Step 4 Remove screws from the UPS front panel, and pull out the UPS. Step 5 Install the new UPS and screw it to the cabinet.
  • Page 282: Replacing Management System Components

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Step 7 Connect the cables to the new battery based on the cable labels. Step 8 Switch the BAT– battery circuit breaker in the power system to ON or reinstall the battery fuse using a fuse extracting unit.
  • Page 283: Replacing An Ecc800-Pro Psu

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-7 Removing the ECC800-Pro main control module Step 5 (Optional) Remove the Micro SD card and SIM card from the corresponding slots of the ECC800-Pro main control module. Step 6 (Optional) Install the removed Micro SD and SIM card in the corresponding slots of the new ECC800-Pro main control module.
  • Page 284: Replacing An Ecc800-Pro Antenna

    FusionModule500 Smart Mini Data Center User Manual 6 O&M ● Materials: a reserved undamaged and undeformed PSU of the appropriate model. Context The PSU is hot-swappable. Procedure Step 1 Push the locking latch in the upper right corner of the PSU panel leftward.
  • Page 285: Replacing A Sim Card

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-10 Replacing an antenna ----End 6.4.3.4 Replacing a SIM Card Prerequisites ● Tools: ESD wrist strap, ESD gloves ● Materials: A spare SIM card of the same model is available and functional.
  • Page 286: Replacing A Camera

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-12 Removing a SIM card Step 5 Insert the new SIM card into the card slot. Figure 6-13 Installing a SIM card Step 6 Insert the ECC800-Pro main control module into the slot.
  • Page 287 FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-14 Removing the transparent cover Step 2 Remove the SD card. Figure 6-15 Removing an SD card Step 3 Remove the monitoring network cable from the camera and remove the camera.
  • Page 288: Replacing A Vcn510

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-16 Removing the camera Step 4 Install the new camera and SD card, reconnect the network cable, and secure the camera to the base using screws. Step 5 Commission the camera by referring to the ECC800-Pro user manual of the appropriate version.
  • Page 289 FusionModule500 Smart Mini Data Center User Manual 6 O&M D ANGER Do not operate with power on. Take appropriate insulation measures. Procedure Step 1 Turn off the power switch of the VCN510, disconnect the power supply of the VCN510, remove the cables from the VCN510, label the cables, and record the original connection positions of the cables.
  • Page 290: Replacing An Ivs1800

    FusionModule500 Smart Mini Data Center User Manual 6 O&M 6.4.3.7 Replacing an IVS1800 Prerequisites ● Recommended tool: Phillips screwdriver ● An IVS1800 needs to be replaced. ● A spare IVS1800 of the same model is available and functional. Context NO TICE Videos cannot be recorded during the replacement of the IVS1800.
  • Page 291: Replacing A Hard Disk For The Ivs1800

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Step 4 Reconnect the cables to the new IVS1800. Step 5 Turn on the power switch of the IVS1800. Step 6 Commissioning the IVS1800. If the video recording function works properly after commissioning, the IVS1800 is functional.
  • Page 292 FusionModule500 Smart Mini Data Center User Manual 6 O&M Step 3 Install a new hard disk. Place the hard disk with ports facing upwards and align the screw holes on the hard disk tray with the hard disk and fasten the screws. Before the installation, ensure that the fastener of the hard disk tray is on a different side from the hard disk port, as shown in the lower left figure.
  • Page 293: Replacing A T/H Sensor (33010516)

    Figure 6-24 Closing the chassis cover Step 4 Observe the hard disk indicator to check whether the hard disk works properly. ----End Follow-up Procedure If the hard disk works abnormally, contact Huawei technical support. 6.4.3.9 Replacing a T/H Sensor (33010516) Prerequisites ●...
  • Page 294: Replacing A Smoke Detector

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Step 2 Remove the cables from the T/H sensor. NO TICE After removing cables, wrap exposed terminals with insulation tape and do not block cable labels. If cable labels are blocked, cables may be connected incorrectly later.
  • Page 295: Replacing A Wlds900 Water Sensor And Water Detection Rope

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-25 Detector position (1) Smoke detector Procedure Step 1 Remove the smoke detector from the base. Step 2 Remove the cables from the smoke detector and apply insulation measures such as wrapping the cables with insulation tape to avoid hazards.
  • Page 296 FusionModule500 Smart Mini Data Center User Manual 6 O&M Context The water detector is installed in the cabinet and bound to the rack rail using cable ties. The binding position is 5 U away from the cabinet bottom. A water sensor consists of a water detection cable, water detector, and conversion cable.
  • Page 297 FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-27 Removing the cover from the water detector Remove the bottom plate of the water detector from the binding position in the cabinet. Install a new water detector in the cabinet by referring to the preceding steps.
  • Page 298: Replacing An Electrode Water Sensor

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Figure 6-29 Connecting a new water detection cable (1) Conversion cable end B, connected to the (2) Water detection cable end A, connected to water detection cable the conversion cable NO TE The water detection cable and conversion cable are interconnected through the male and female connectors.
  • Page 299: Technical Specifications

    FusionModule500 Smart Mini Data Center User Manual 7 Technical Specifications Technical Specifications Table 7-1 Key technical specifications Item Specifications Module dimensions (H x W x D) Fully enclosed indoor cabinet: 2000 x (mm) 600 x 1350 Number of cabinets 1 PCS...
  • Page 300: A Equipment Derating Coefficients

    FusionModule500 Smart Mini Data Center User Manual A Equipment Derating Coefficients Equipment Derating Coefficients NO TE The coefficients listed in the Table A-1 are based on the dry air density being 1.225 kg/m (sea level +15ºC). Table A-1 Derating coefficients of the UPS2000-G...
  • Page 301: B Acronyms And Abbreviations

    FusionModule500 Smart Mini Data Center User Manual B Acronyms and Abbreviations Acronyms and Abbreviations alternate current Auto Transformer Switch ATSE Auto Transformer Switch Equipment Battery Interface Module Communication Interface Module direct current International Electrotechnical Commission miniature circuit breaker SNMP Simple Network Management Protocol...
  • Page 302 FusionModule500 Smart Mini Data Center User Manual B Acronyms and Abbreviations uninterruptible power system Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd.