For security purposes, you are advised to set Permission to Read.
Record the User Name, MD5/SHA Password, and DES/AES Password for
using when creating a UPS2000-G on the NetEco.
Figure 6-51 Setting SNMP parameters_03
Click Add in NMS Address and Permission Settings.
In the displayed Add NMS Address Info dialog box, set related parameters
and click Add.
Enter the IP address of the NetEco server in the NMS addr. text box.
For security purposes, you are advised to set Permission to Read.
Figure 6-52 Adding the NMS IP address
Click Add under SNMP TRAP.
In the displayed Add SNMP Trap dialog box, set related parameters and click
Add.
Enter the IP address of the NetEco server in the Trap Address text box.
Set Trap port to 162.