Setting Rs485 Parameters For The Ecc800-Pro Collector - Huawei iMaster NetEco V600R021C10 Device Installation And Commissioning Manual

Table of Contents

Advertisement

iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
Figure 6-63 Setting the system type
----End

6.5.1.4 Setting RS485 Parameters for the ECC800-Pro Collector

Prerequisites
Context
To ensure the normal connection between the ECC800-Pro collector and devices,
properly set the RS485 parameters for the ECC800-Pro collector, such as
BaudRate, DataBit, StopBit and Parity. Ensure these parameters stay consistent
with those of the devices.
This section describes how to set RS485 port parameters for the COM1 port on the
ECC800-Pro.
Procedure
Step 1 Set RS485 port parameters on the WebUI of the ECC800-Pro collector.
1.
2.
3.
4.
5.
Issue 02 (2021-05-12)
You have obtained the IP address and login user name and password for the
ECC800-Pro collector.
A PC with an IP address in the same network segment as the ECC800-Pro
collector is prepared, and the PC has been connected to the ECC800-Pro
collector over a switch.
Use a PC, enter https://XX.XX.XX.XX in the address bar to log in to the WebUI
of the ECC800-Pro collector.
NO TE
– XX.XX.XX.XX indicates the IP address of the collector.
– To ensure the security of data transmission, the NetEco transmits data after
encrypting it over the Secure Sockets Layer (SSL).
Choose Monitoring > System > ECC800 > Running Parameters.
Click Unhide All Advanced Signals.
Click COM Port Parameters.
Select a value from the Baud rate, Data bit, Stop bit, and Parity drop-down
list boxes, and click Submit, as shown in
Copyright © Huawei Technologies Co., Ltd.