Device Installation and Commissioning Guide (Data
Center)
address is set in binary coding format in the range of 1–63. The first bit is the least
significant, and the sixth bit is the most significant. ON indicates 1 and OFF
indicates 0. The address range is 1–63.
Figure 3-26 DIP switch settings for T/H sensors
Step 3 Connect the communications cables to the T/H sensors.
Figure 3-27 Cable connections to T/H sensors
Issue 02 (2021-05-12)
NO TE
The numbers indicate the DIP switch settings of the T/H sensors.
Copyright © Huawei Technologies Co., Ltd.
3 Installing Devices
36