Huawei FusionDC1000A Product Description
Huawei FusionDC1000A Product Description

Huawei FusionDC1000A Product Description

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

Quick Links

FusionDC1000A Prefabricated All-in-One Data
Center
V100R021C00
Product Description (IT Scenario)
Issue
04
Date
2023-11-10
HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei FusionDC1000A

  • Page 1 FusionDC1000A Prefabricated All-in-One Data Center V100R021C00 Product Description (IT Scenario) Issue Date 2023-11-10 HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    About This Document About This Document Purpose This document describes the FusionDC1000A prefabricated all-in-one data center (FusionDC1000 for short) solution in terms of its overview, typical application scenarios, product architecture, and key technical specifications, helping readers to systematically understand the FusionDC1000.
  • Page 4 This issue is the third official release. Optimized the content. 2022-12-15 This issue is the second official release. Optimized the content. 2021-04-20 This issue is the first official release. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 5: Table Of Contents

    4.2 Integrated UPS..................................27 4.2.1 Product Structure................................27 4.2.2 Technical Specifications..............................29 4.3 rPDU......................................32 4.4 SmartLi Cabinet Description............................. 33 4.5 SmartLi Components................................34 4.5.1 MDU....................................... 34 4.5.2 Monitoring Interface Unit...............................35 Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 6 6.11 Door Status Switch................................94 6.12 Emergency Door Release Button..........................95 6.13 Exit Button.................................... 96 6.14 Magnetic Lock..................................96 6.15 Non-Location-Type Water Sensor..........................97 6.16 PAD......................................98 7 Fire Extinguishing System....................99 Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 7 7.10 Fire Alarm Horn Strobe..............................110 7.11 Warning Sign..................................111 8 Surge Protection and Grounding..................113 8.1 Surge Protection................................. 113 8.2 Grounding..................................... 113 9 Integrated Cabling......................115 A Acronyms and Abbreviations................... 117 Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 8: Overview

    Overview 1.1 Positioning Huawei has developed the FusionDC1000, a green data center solution, based on a thorough study on the reform and impact of the cloud computing to traditional data centers and the practical experience of dozens of global cloud computing centers.
  • Page 9 Local PAD 3D NMS + app view, power supply/cooling 2D link visibility inside the pre-fab. module. ● Early warning, rack resource automation, management automation, and cooling/power linkage to eliminate hot spots. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 10: Typical Application Scenarios And Typical Configuration

    The FusionDC1000 can be deployed as a small integrated data center (IDC) for enterprises in diverse environments such as the seaside, industrial parks, Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 11: Typical Configuration

    ASD (optional), and emergency light indicator Monitori ECC800-Pro, smart ETH gateway, smart module actuator, water sensor, PAD, camera, IC card reader, door status sensor, and magnetic system lock Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 12: Key Technical Specifications

    You can move the mounting bar on the front door to install a device with a depth of 850 mm. ● 1100 mm deep cabinet: A device with a depth of less than or equal to 750 mm can be installed. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 13 Long aisle: 640 mm; cold aisle: 1150 mm; hot aisle: ≥ 510 mm width Cabinet The battery cabinet can slide 200 mm in both directions. Other cabinets are type fixed. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 14 V/9 Ah) x 8 V/9 Ah) x 16 rPDU IEC standard CCC standard type Cooling Cooling 25 kW @ 37°C, 20% RH/35°C system capacity Redunda 3+1 redundancy configura tion Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 15 The 100 mm thick rock wool panel can withstand fire for 60 minutes. Monito Pre-fab. Default IC card door status sensor ring module system access control Aisle Not supported access control Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 16 ● Batteries can be stored without power-on for a maximum of 90 days. If the storage period exceeds 90 days, recharge the batteries promptly. ● The PAD storage temperature ranges from –20°C to +45°C. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 17: Structural System

    3.1 Pre-fab. Module Figure 3-1 Appearance 1 (1) End door (for maintaining outdoor units) (2) Lock rod (3) Ventilation window for the outdoor unit (4) Pre-fab. module feeder windows compartment Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 18: Pre-Fab. Module Thermal Insulation Structure

    The current standard pre-fab. module coating solution passes the 1440-hour salt spray test. According to the ISO12944 standard, the pre-fab. module provides the VH protection level in C3 and C4 environments. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 19: Pre-Fab. Module Doors

    When the door is open, the door, door frame, and mechanical parts can withstand the door weight and will not deform permanently within 48 hours with a static load of 15 kg at any part. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 20: Pre-Fab. Module Interior Layout

    (1) Smart cooling product (2) IT cabinet (3) Smart cooling product outdoor unit compartment indoor unit (4) Cold aisle (5) Integrated UPS (6) Hot aisle (7) Battery cabinet (8) Entrance room Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 21: Components Inside The Pre-Fab. Module

    Cable trays are secured to the aluminum guide rails using sliding nuts. ● The load-bearing capacity of cable trays is 150 kg/m. Figure 3-6 Overhead cable tray (1) Overhead cable tray Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 22: Suspended Ceiling

    3.6.3 IT Cabinet A cabinet provides stable installation space for servers, thereby ensuring safe operation of servers. The cabinet dimensions are unified, and both front and rear air channels are designed. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 23 ● 2000 mm x 600 mm x 1100 mm Color Black (PANTONE426C/RAL9005) Material High-intensity class A carbon cold rolled steel plate and zinc-coated steel plate Air channel Front and rear air channels Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 24: Raised Floor

    The legs can be adjusted in height, and are galvanized to provide efficient anti-corrosion performance. ● The compression strength of both the raised floor and legs is greater than 1500 kg/m Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 25: Aisle Sliding Door

    The dimensions of a sliding door are 2250.8 mm (H) x 1928 mm (W) and the glass door is 755.0 mm wide. Figure 3-10 Aisle sliding door (unit: mm) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 26: Cabinet Base

    Pipe feature an anti-backflow design, adapting to different configuration demands. Fire extinguishing devices on the pre-fab. module exterior meet sealing conditions. Figure 3-12 External ports (unit: mm) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 27 No. 11 is used for the ECC800-Pro 4G antenna. Figure 3-14 Positions of the reserved ports (1) Port reserved for the humidifier water refill (2) Port reserved for the condensate drainpipe pipe Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 28 The port reserved for the condensate drainpipe is a DN25 PP-R pipe port. ● When the temperature is lower than 0°C, take thermal insulation measures for the water refill port and drain port. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 29: Power Supply And Distribution System

    ECC800-Pro, and other auxiliary devices inside the pre-fab. module. The power supply and distribution system consists of the integrated UPS, power PDB, smart module actuator, AC PDB, and rPDU. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 30 FusionDC1000A Prefabricated All-in-One Data Center Product Description (IT Scenario) 4 Power Supply and Distribution System N+X Scenario Figure 4-1 System conceptual diagram (N+X scenario) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 31 Figure 4-2 Layout of power supply and distribution devices (N+X scenario) (1) Integrated UPS (2) SmartLi lithium (3) Power PDB (4) AC PDB battery cabinet or lead-acid battery cabinet Figure 4-3 Power density (N+X scenario) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 32 FusionDC1000A Prefabricated All-in-One Data Center Product Description (IT Scenario) 4 Power Supply and Distribution System 2N Scenario Figure 4-4 System conceptual diagram (2N scenario) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 33 Figure 4-5 System conceptual diagram (2N scenario, Tier III) Figure 4-6 Layout of power supply and distribution devices (2N scenario) (1) Integrated UPS (2) SmartLi (3) Power PDB (4) AC PDB (in the pre- fab. module) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 34: Integrated Ups

    ● The appearance of the UPS5000-E-125K-HASBS is similar to that of the UPS5000-E-125K- HASBS-01, but the number of power modules is different. Figure 4-8 UPS5000-E-60K-HABBS front view (1) Power input status (2) Input circuit breaker (3) Lighting circuit breaker indicator Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 35 (7) UPS input circuit breaker (8) UPS maintenance bypass (9) Control module circuit breaker (10) Bypass module (11) Power modules (12) MDU (13) Power distribution (14) UPS output circuit breaker - monitoring board Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 36: Technical Specifications

    IEC 62040-3. The upper limit of the altitude is 4000 m. Table 4-3 Safety and EMC Item Specifications Safety compliance EN 62040-1, 2013 IEC 62040-1, 2013 Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 37 Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage) Input frequency range 50/60 Hz ±6 Hz (adjustable with a tolerance of 0.5–6 Hz, ±2 Hz by default) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 38 Derating coefficient of ● 40 A circuit breaker: 0.75 output circuit breakers ● 63 A circuit breaker: 0.7 Table 4-7 System electrical specifications Item Specifications System efficiency 95% (linear load) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 39: Rpdu

    ● If the power density of a single IT cabinet is 9 kW, configure the half-height rPDU. Figure 4-10 IEC full-height rPDU Figure 4-11 IEC half-height rPDU Figure 4-12 Chinese-standard full-height rPDU (unit: mm) Figure 4-13 Chinese-standard half-height rPDU (unit: mm) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 40: Smartli Cabinet Description

    (7) Slots for battery modules (8) Communications cable (9) Monitoring display unit outlet (MDU, available only on the master cabinet) (10) Carbon monoxide gas (11) Document holder (12) MCCB lever sensor (optional) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 41: Smartli Components

    (SOH), and temperature reported by the BCU, and save data and alarm information locally. NO TE The ports of the MDU are located on the side and rear of the display panel. Figure 4-15 MDU Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 42: Monitoring Interface Unit

    The monitoring interface unit provides ports for parallel connection of battery cabinets, an FE port, an RS485 port, EPO ports, two groups of output dry contacts, and two groups of input dry contacts (reserved). Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 43 Output dry Function setting of output dry contact contact 2 for the lithium battery cabinet. The maximum voltage and current are 30 V DC/1 A or 60 V DC/0.5 A. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 44: Bcu

    Converts the power of battery strings. When the consistency between battery strings is poor, the BCU controls the current balance between battery strings through voltage boosting and balance adjustment to implement active Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 45 UPS can be cold started. Blinking at intervals of ● The power button is pressed down. 0.5s (on for 0.25s and ● An upgrade is in progress. off for 0.25s) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 46: Battery Module

    The BMU provides the following functions: ● Battery voltage measurement and alarm ● Battery temperature measurement and alarm ● Battery voltage balancing ● CAN communication between battery modules Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 47: Carbon Monoxide Gas Sensor

    The sensor detects the concentration of carbon monoxide in the cabinet to determine whether carbon monoxide is released from battery modules because the vents are opened due to thermal runaway. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 48 (1) DIP switch (2) RS485 communications ports Figure 4-20 RS485 port pins Table 4-14 RS485 port definition Signal Description RS485+ RS485– V+: power supply, positive RS485+ RS485– V–: power supply, negative Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 49: Module

    Blinking at intervals of 2s The backhaul module (on for 1.8s and off for 0.2s) has successfully registered with the network or is in the standby state. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 50: Lead-Acid Battery Pack

    Figure 4-22 Battery pack Table 4-16 Battery pack technical specifications Battery Pack Dimensions (H x W x D) Weight Specifications 9 Ah 130 mm x 430 mm x 685 70.5 kg Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 51: Lead-Acid Battery Cabinet

    42 U available space Weight 180 kg (without battery packs) Static load 1500 kg IP rating IP20 4.8 Power PDB Figure 4-23 Open door view of a power PDB Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 52: Ac Pdb

    Table 4-19 Technical specifications Item Specifications External dimensions (H x W x D) 222 mm x 300 mm x 86 mm Rated operating voltage 220 V AC Rated frequency 50 Hz/60 Hz Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 53 One 1-pole 10 A MCB+YO+AUX+relay Operating temperature –5°C to +40°C Operating humidity 5%–95% RH Installation mode Installed on the wall Cabling mode Routed in and out from the top Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 54: Cooling System

    Fresh air fans are deployed to introduce fresh air from outside of the module to ensure the fresh air ventilation volume required by the personnel inside the module. Figure 5-1 Cooling principle Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 55 Figure 5-2 Cooling system diagram Figure 5-3 Temperature simulation of the cooling system graph Figure 5-4 Layout of cooling components (1) Smart cooling product outdoor unit (2) Smart cooling product indoor unit Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 56 Figure 5-6 Fresh air ventilation diagram (1) Air inlet window (2) Air exhaust window (3) Fans Figure 5-7 High temperature derating curve for IT AIO NO TE The return air temperature is 37.8°C. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 57: Netcol5000-A025 Smart Cooling Product

    Figure 5-8 Indoor unit Dimensions Table 5-1 Dimensions of the NetCol5000-A025 indoor unit Cabinet H (mm) x W (mm) x D (mm) Expansion Method Dimensions Standard 2000 x 300 x 1100 dimensions Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 58 The indoor unit of the 25 kW smart cooling product mainly consists of a compressor, oil separator, fan, heat exchanger, electronic expansion valve, check valve, filter dryer, sight glass, electric heater (optional), wet film humidifier (optional), and water pump (optional). Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 59 The throttling device uses a miniature controller to control the operation of the step motor, thereby changing the pass-through area of the EEV to regulate the flow of refrigerant. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 60: Operating Environment Specifications

    ● Work with NetCol500-A040MS1E0 (with a low temperature component): –40°C to +45°C Protection level ● Outdoor unit: IPX5 Altitude 0–4000 m, derated at above 1000 m. For details about derating data, contact Huawei technical support. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 61 8 Thermal insulation foam ≥ 13 mm thickness Inner diameter of thermal Liquid pipe: 16 mm insulation foam Gas pipe: 19 mm Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 62: Technical Specifications

    (RCCB) that is insensitive to single-phase DC pulsation and transient impulse current. Note: If certain conditions are not met, contact Huawei technical support. 5.2.3 Technical Specifications Table 5-5 General specifications Item...
  • Page 63: Dehumidifier

    Heating Available Humidification Available Pipe routing Top and bottom pipe routing Condensate pump Water pump lift 5.3 Dehumidifier Figure 5-11 Dehumidifier Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 64: T/H Sensor

    5.4 T/H Sensor Figure 5-12 Appearance The T/H sensor provides RJ45 ports. NO TE The appearance of the T/H sensor delivered onsite may vary. Figure 5-13 RJ45 port pins Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 65: Outdoor Unit

    9–16 V DC Storage temperature –40°C to +70°C Output RS485 5.5 Outdoor Unit Figure 5-14 Composition of the NetCol500 outdoor unit (1) Electric control box (2) Rack (3) Fan Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 66 RoHS, REACH, CE Storage temperature –40°C to +70°C Storage humidity 5%–95% RH (non-condensing) Altitude 0–4000 m, derated at above 1000 m. For details about derating data, contact Huawei technical support. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 67: Fan

    ● Pressure preservation is performed on the condenser before delivery, and the pipe ports are properly sealed to prevent foreign matter from entry. 5.6 Fan Figure 5-16 Fan Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 68: Low Temperature Component

    When detecting that the condensing pressure exceeds the threshold, the pressure stabilizing valve automatically closes the bypass. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 69 828 mm x 470 mm x 300 mm (without packing) Expansion bolt hole M12x60 Storage temperature –40°C to +70°C Storage humidity 5%–95% RH (non-condensing) Maximum operating pressure 4.35 MPa Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 70: Management System

    (O&M), security management, log management, and system management. ● The NetEco is the centralized O&M part of the Huawei data center infrastructure management solution. The system uses an open architecture and connects to various types of devices using device access packages.
  • Page 71 LAN switch. Table 6-1 Management system configurations Function ECC800-Pro NetEco Client 16 PCS One license manages up to 25 smart nodes. authorization Work order management Energy efficiency management Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 72 This feature provides the electricity fee policy function. You can customize the electricity price per unit to learn the power consumption cost and trends of the system in real time. Capacity management Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 73: Ecc800-Pro

    You can configure the ECC800-Pro collector in the following two manners: Configuration 1 (typical configuration): one PSU and one main control module Configuration 2: two PSUs and one main control module. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 74 (AC_INPUT1 and AC_INPUT2) and two DC output ports (DC_OUT1 and DC_OUT2). Table 6-2 provides the power port pin definitions. Table 6-2 Power port pin definitions Port Type Silk Description Screen RTN+ 48V+ RTN- 48V GND Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 75: Technical Specifications

    ● Output voltage: 13–15 V DC (rated voltage: 14.5 V DC) (RJ45) ● Supports one active DO port. ● The power supply can be switched on or off and is on by default. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 76 ● The WLAN port on the main control module (02312QAA or 02312QAA-001) is reserved and is temporarily unavailable. ● The WLAN port on the main control module (02312QAA-004) can be connected to a WLAN antenna for WLAN communication. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 77 Table 6-5 ECC800-Pro structural specifications Item Specifications Dimensions (H x W x D) 43.6 mm x 442 mm x 330 mm Weight 7.5 kg (dual PSUs + main control module) Color Black Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 78: Main Control Module

    (5) COM1/AIDI_4 (6) COM3/12V (7) WAN1 (8) LAN1/POE (9) LAN2/POE (10) WAN2 (11) COM4/CAN (12) COM2/AIDI_5 (13) AIDI_3 (14) DO/12V (15) RF_Z (802.15.4) (16) WLAN (17) 4G (18) SW button Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 79 (LAN1/PoE and LAN2/PoE). Table 6-8 GE port pin definitions Item Description Pin 1 GE1+ sequence Pin 2 GE1– Pin 3 GE2+ Pin 4 GE3+ Pin 5 GE3– Pin 6 GE2– Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 80 Table 6-10 COM3/12V port pin definitions Item Description Pin 1 RS485+ sequence Pin 2 RS485– Pin 3 12 V DC_OUT Pin 4 RS485+ Pin 5 RS485– Pin 6 Pin 7 Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 81 Pin 7 Pin 8 Indicator Green Power output indicator indicator ● Steady on: The 12 V DC output is normal. ● Off: No 12 V DC output is provided. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 82 Table 6-14 Indicators on the ECC800-Pro main control module Indica Color Name Status Description Green Running status Steady on The power supply is normal, indicator the program is being loaded. The power supply is abnormal. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 83 3s to 5s to exit the pairing mode; intervals. or the system automatically exits the pairing mode after 30 minutes. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 84: Psu

    Table 6-16 PSU indicator description Indicator Color Name Status Description Green Power Steady on The PSU has input power. indicator The PSU has no input power or is faulty. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 85 1s and then off for 1s). Fault Steady on The PSU locks out due to indicator output overvoltage. The PSU has no output due to internal faults. The PSU is normal. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 86: Uim20A Expansion Module

    RTU communication) Table 6-17 Structural specifications of the UIM20A expansion module Item Specifications Width 120 mm Depth 200 mm Height 43 mm Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 87 Communications Ports The following table describes the pin definitions for ports COM1/AIDI_1 to COM8/ AIDI_8. Table 6-19 Pin definitions for ports COM1/AIDI_1 to COM8/AIDI_8 Item Description Pin 1 RS485+ sequence Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 88 The board is not running. Blinking The ECC800-Pro is successfully registered, and the at long software runs properly (blinking at long intervals (0.5 intervals Hz), on for 1s and then off for 1s). Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 89: Smart Eth Gateway

    (3) PoE_1–2 ports (4) PoE_3–4 ports power port signal port (5) 48V_OUT1 power (6) 48V_OUT2 power (7) FE_2 cascading (8) PWR_OUT output port output port signal port cascading power port Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 90: Ac Actuator

    (disabled by default), or signals from the light button. It also provides a charging port for the PAD (AC OUT2). Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 91 One wireless communication port that complies with communicat IEEE802.15.4 RS485 serial One route of dual RS485 ports, not isolated (reserved) port AI/DI Two AI/DI dry contacts, connecting to two light buttons detection Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 92 0.05s and then off for 0.05s) and then turns off for 0.5s. The cycle lasts for 5s. Alarm Steady on A system failure alarm is indicator generated. No system alarm is generated. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 93: Access Actuator

    It has access right management, access event record, and alarm record functions. Figure 6-12 Access actuator (1) 48 V power port (2) PoE port (3) RS485 port COM2 Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 94 ● Hold down the button for 1–5 seconds to search for a network and start networking. ● Hold down the button for more than 10 seconds to clear network parameters. Address DIP 4-pin address DIP switch switch E-label Supported Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 95 0.5s (blinking at 10 Hz, on for 0.05s and then off for 0.05s) and then turns off for 0.5s. The cycle lasts for Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 96 The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/ COM). Table 6-28 lists the LOCK/GND/GATE/COM port pin definitions. Table 6-28 LOCK/GND/GATE/COM port pin definitions Item Description LOCK/GND LOCK 12V_OUT (control magnetic locks) pin sequence Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 97: Ip Camera

    A WiFi module can be installed at the USB port on the main control module (02312QAA or 02312QAA-001) to provide WiFi signals for devices such as the PAD to exchange data with the ECC800-Pro. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 98: Wlds900 Water Sensor (Bom Number: 33010352)

    < 0.8 W Maximum number of connected devices 6.9 WLDS900 Water Sensor (BOM Number: 33010352) The WLDS900 water sensor consists of the water detection cable, water detector, and conversion cable. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 99 Table 6-31 Technical specifications of the WLDS900 water sensor Item Specifications Operating 12 V DC (9–16 V DC) voltage Operating –20°C to +70°C temperature Storage –40°C to +85°C temperature Humidity 10%–80% RH (non-condensing) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 100: Ic Card Reader

    –40°C to +85°C temperature Operating 5%–95% RH (non-condensing) humidity Operating 7–30 V DC voltage Current 580 mA Sensing range 3–5 cm Card reading ≤ 0.1s duration Operating 13.56 MHz frequency Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 101: Door Status Switch

    10 W Impedance ≤ 0.3 Ω Node voltage endurance 150 V DC Maximum current 500 mA Opening distance ≥ 20 mm, ≤ 45 mm (test in an environment without interference) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 102: Emergency Door Release Button

    Breaking the glass Switch status Normally open (NO)/normally closed (NC) Operating temperature –20°C to +55°C Operating humidity 0%–95% RH Alarm Reports Boolean value alarm signals when the glass is broken. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 103: Exit Button

    Enclosure IP rating IP54 6.14 Magnetic Lock Figure 6-20 Single door magnetic lock Table 6-36 Technical specifications of the single-door magnetic lock Item Specifications Operating voltage 10–14 V DC Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 104: Non-Location-Type Water Sensor

    Figure 6-21 Water sensor Table 6-37 Water sensor technical specifications Item Specifications Operating voltage 12 V DC (9–16 V DC) Insulation resistance > 500 megohms Operating environment –20°C to +70°C Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 105: Pad

    Figure 6-22 PAD The PAD is a capacitive screen which supports multi-touch. Huawei PAD screen size is 8–12 inches. The PAD uses Android 4.0 or later, and has a memory of 2 GB or more. NO TE If a non-standard PAD is selected, confirm with Huawei engineers.
  • Page 106: Fire Extinguishing System

    At the same time, the extinguishant control panel automatically reports alarms. Figure 7-1 Conceptual diagram of the fire extinguishing system Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 107 Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 108 Shall be configured with in-room CO sensors, smoke sensors, and temperature sensors. At least two sensors of each type shall be configured, and the automatic fire alarm system should be enabled. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 109 A battery fire may reignite after having been extinguished. After the fire is extinguished, cool the batteries for at least 24 hours and observe them using a thermal imager to ensure that the batteries decrease to room temperature. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 110: Extinguishant Control Panel (Ce)

    230 V AC±10%, 50 Hz AC input power ≤ 100 W DC backup power 24 V DC 24 V DC output Operating temperature –30°C to +55°C Operating humidity ≤ 95% RH (non-condensing) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 111: Extinguishant Control Panel

    When the FusionDC1000 catches fire, a lot of smoke is generated and the temperature rises sharply. The smoke detector and heat detector send fire alarm signals to the extinguishant control panel, which generates a voltage to start the Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 112: Smoke Sensor

    Cylinder volume 38 L Operating Temperature –20°C to +55°C environment Humidity ≤ 95% RH (non-condensing at 40°C) 7.4 Smoke Sensor Smoke sensors are used to detect the smoke concentration. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 113: Heat Detector

    The detector issues an alarm signal in the form of circuit current change, and provides the alarm locking function. The alarm can be reset only by short- time power-off. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 114: Optional) Asd

    ASD blinks and sends an alarm signal to the monitoring module. The ASD consists of the detection unit (ASD-532) and air sampling pipes with small holes. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 115: Emergency Light And Escape Sign

    The device is used for exit lighting and indication in the case of an emergency power failure in the equipment room. It is chargeable and provides overcharge protection. Figure 7-10 Emergency light and escape sign Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 116: Fire Alarm Bell

    Figure 7-11 Fire alarm bell Table 7-7 Technical specifications of the fire alarm bell Item Specifications Operating voltage 20.4–27.6 V DC Operating current ≤ 11 mA Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 117: Extinguishant Abort Button

    The device can generate audible alarm signals after being connected to a 24 V DC power supply. It can be used with a fire alarm control panel through an output Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 118: Warning Sign

    When the extinguishant control device is started, the warning sign blinks, displays FIRE ALARM DO NOT ENTER, and generates a sound to warn onsite personnel away from the protected area. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 119 Dimensions (H x W x D) 220 mm x 330 mm x 95 mm Operating voltage 15–30 V DC Operating temperature –15°C to +40°C Operating humidity ≤ 95% RH Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 120: Surge Protection And Grounding

    External Grounding M12 bolt ground points are evenly located on the pre-fab. module exterior. Ensure that the two ground points are connected to the ground grid. There are two Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 121 Product Description (IT Scenario) 8 Surge Protection and Grounding ground points on the pre-fab. module exterior. The ground resistance is within 10 ohms. Figure 8-2 Pre-fab. module ground points (unit: mm) Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 122: Integrated Cabling

    Cable trays on the top of the pre-fab. module are separate from cabinets, and can be moved horizontally along the width direction on the top of the pre-fab. module. Strong- and weak-current cables are routed separately. Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 123 (1) Signal cable (2) Power cable (3) Cable from the UPS to the battery cabinet (4) Mains inlet port (5) Cables for indoor and outdoor units of smart cooling products Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 124: A Acronyms And Abbreviations

    Acronyms and Abbreviations application aspirating smoke detector automatic transfer switch Conformite Europende International Organization for Standardization integrated data center International Electrotechnical Commission miniature circuit breaker MCCB molded case circuit breaker Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.
  • Page 125 Network Ecosystem power usage effectiveness RoHS Restriction of the Use of Certain Hazardous Substances REACH Registration, Evaluation, Authorization and Restriction of Chemicals SNMP Simple Network Management Protocol static transfer switch Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd.