Huawei iMaster NetEco V600R021C10 Device Installation And Commissioning Manual page 236

Table of Contents

Advertisement

iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
Table 6-25 SNMPv3 device parameter description
Parameter
Managed Object
Name
IP
Port
Security Name
Authentication
Protocol
Authentication
Password
Privacy Protocol
Privacy Password
Step 8 Click
Step 9 Click Connection test to start the connection test.
----End
Issue 02 (2021-05-12)
NO TE
SNMPv1 and SNMPv2 are insecure. SNMPv3 is recommended because it is more secure.
Description
Device name
Set this parameter to the device IP address.
Set this parameter to the port number of the device. (set to
161 by default)
Set this parameter to the user name added in SNMPv3 on
the device.
Set this parameter to the authentication protocol set on the
device. The default selection is SHA.
Support SHA and MD5 agreement.
NOTE
MD5 is an insecure protocol. SHA is recommended.
Set this parameter to the authentication algorithm key
configured on the subdevice.
Value range: a–z, A–Z, 0–9, _ (8–15 characters, at least two
types of characters, different from the user name or its
reverse)
Set this parameter to the privacy protocol set on the device.
The default selection is AES128.
Support CBC_DES, AES128, AES192, and AES256
agreement.
NOTE
DES is an insecure protocol. AES is recommended.
Set this parameter to the proprietary protocol key
configured on the device.
Value range: a–z, A–Z, 0–9, _ (8–15 characters, at least two
types of characters, different from the user name or its
reverse)
NOTE
You are advised to set Authentication Password and Privacy
Password to different values.
on the toolbar to save the device information.
Copyright © Huawei Technologies Co., Ltd.
6 Adding Devices
225

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents