3.
4.
5.
6.
Issue 02 (2021-05-12)
In the SNMPv3 area, click Add.
In the displayed SNMPv3 dialog box, set SNMPv3 parameters, and click
Confirm.
You are advised to set MD5/SHA password and DES/AES password to
different values.
MD5 is an insecure protocol. SHA is recommended. DES is an insecure
protocol. AES is recommended.
Record the User Name, MD5/SHA password, and DES/AES password for
using when creating a UPS on the NetEco.
Figure 6-41 Setting SNMPv3 parameters
In the SNMP Trap area, click Add.
In the displayed SNMP Trap dialog box, set SNMP trap parameters, and click
Confirm.
Enter the IP address of the NetEco server in the Trap Target Address text
box.
Set Trap Port to 162.
Copyright © Huawei Technologies Co., Ltd.
6 Adding Devices
197