Ecc800-Pro; Product Configuration - Huawei iMaster NetEco V600R021C10 Device Installation And Commissioning Manual

Table of Contents

Advertisement

iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
Figure 4-20 Preparing the RS485 monitoring cable for ECC800-Pro collector
Preparing a Dry Contact Monitoring Cable
The method of preparing a dry contact monitoring cable is similar to the method
of preparing the RS485 monitoring cable. Prepare cord end terminals on both ends
of each required core wire based on the number of dry contacts.

4.3.2 ECC800-Pro

4.3.2.1 Product Configuration

The ECC800-Pro data center controller is mainly used to monitor the devices and
environment in a data center. It consists of the power module and main control
module, which are pluggable.
You can configure the ECC800-Pro collector in the following two manners:
Configuration 1 (typical configuration): one power module and one main control
module
Configuration 2: two power modules and one main control module.
Issue 02 (2021-05-12)
NO TE
● In configuration 1, install a filler panel in slot 2.
● In configuration 2, install power modules in slots 1 and 2.
Copyright © Huawei Technologies Co., Ltd.
4 Connecting Monitoring Cables to Devices
90