Device Installation and Commissioning Guide (Data
Center)
Procedure
Step 1 Change the NetEco IP address.
1.
2.
3.
Step 2 Update the NetEco IP address on the ECC800-Pro WebUI.
1.
2.
3.
Step 3 Modify the UPS2000-G/UPS2000-H SNMP trap parameters (WebUI 1)
1.
2.
3.
4.
Issue 02 (2021-05-12)
In the browser address bar, enter https://client IP address of PowerEcho:31945,
enter the User Name and Password, and press Enter to access the
PowerEcho client.
NO TE
The default user name for PowerEcho is admin and the preset password is
Changeme_123.
On PowerEcho, choose Maintenance > Network Configuration > Configure
IP Address from the main menu.
Choose Modify IP Address, select the NetEco to be configured, and click Edit,
set IP Address,Subnet Mask/Prefix Length and NIC Usage, and click Apply.
NO TE
After you change IP address of a database node, the product services and the databases
will be automatically restarted.
Log in to the ECC800-Pro WebUI.
Set NetEco communications parameters.
Table 8-1 NetEco communications parameters
Path
Parameter
System
Server IP
Settings >
NMS
Application
> NetEco >
Communica
tion
Parameters
Port number
Network
port for link
setup
Click Submit.
Log in to the UPS2000-G WebUI.
Choose System Settings > SNMP Settings.
In the SNMP Trap area, if Trap Target Address is the same as the NetEco IP
address before the modification, select this row and click Delete.
In the SNMP Trap area, click Add.
Copyright © Huawei Technologies Co., Ltd.
Default
Setting
Value
192.168.8
IP address of the primary NetEco
.11
server
NOTE
The NetEco IP address and the
ECC800-Pro IP address must be
configured in the same network to
ensure normal connection between
the NetEco and the ECC800-Pro.
31220
31220
WAN_1
WAN_1 or WAN_2
8 FAQ
322