Setting Device Monitoring Parameters Of An No/Nc Dry Contact On The Ecc800-Pro Web - Huawei iMaster NetEco V600R021C10 Device Installation And Commissioning Manual

Table of Contents

Advertisement

iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
Step 3 Set AI/DI_1 to Enable.
Step 4 Click Submit.
Step 5 Check whether AI/DI_1 sensor type is automatically identified. The following uses
Smoke sensor as an example.
Figure 6-70 Setting a sensor type for a dry contact
Step 6 Click Unhide All Advanced Signals, then click Power Supply Parameters. Ensure
that III power supply enable(AIDI_1/DO) is Yes.
Step 7 Click Submit.
----End
6.5.2.1.3 Setting Device Monitoring Parameters of an NO/NC Dry Contact on the
ECC800-Pro Web
After a normally open (NO) or normally closed (NC) dry contact is connected to
the AI/DI port of an ECC800-Pro collector, you need to set device parameters of
the NO or NC dry contact on the WebUI.
Prerequisites
Context
Procedure
Step 1 Log in to the WebUI of the ECC800-Pro collector.
Step 2 Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1 Port
Settings.
Step 3 Set AI/DI_1 to Enable.
Issue 02 (2021-05-12)
You have obtained the IP address, and login user name and password for the
ECC800-Pro collector.
A PC with an IP address in the same network segment as the ECC800-Pro
collector is prepared, and the PC has been connected to the ECC800-Pro
collector over a switch.
An NO or NC dry contact is a device whose normal status signal is open (or
closed) and whose alarm signal is closed (or open), such as a skylight
controller.
This section describes how to set skylight controller monitoring parameters
when a skylight controller is connected to the AI/DI_1 port of the ECC800-Pro
collector. Set the parameters based on the actual port connected to the
skylight controller onsite.
Copyright © Huawei Technologies Co., Ltd.
6 Adding Devices
243