Adding The Access Management System; Setting Monitoring Parameters For The A8802Rs Access Controller; Creating An Access Controller On The Neteco - Huawei iMaster NetEco V600R021C10 Device Installation And Commissioning Manual

Table of Contents

Advertisement

iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
Parameter
Port
Device Address
Step 8 Click
Step 9 Click Connection test to start the connection test.
----End

6.5.3 Adding the Access Management System

6.5.3.1 Setting Monitoring Parameters for the A8802RS Access Controller

Procedure
Step 1 Set the address of the access controller using the DIP toggle switches, set the
device address to 0 by default, as shown in
Table 6-40 Setting the address of the access controller
Device Address
0
1
2
3
Step 2 Set the baud rate of the access controller to 19200. The preset data bit, stop bit,
and check bit are 8, 1, and none respectively. For ECC800-Pro collector settings,
see
----End

6.5.3.2 Creating an Access Controller on the NetEco

This section describes how to create an access controller on the NetEco.
Prerequisites
Issue 02 (2021-05-12)
Description
Set this parameter to the port through which the device
connects to the collector.
For details about the ports on the ECC800-Pro collector, see
6.5.1.4 Setting RS485 Parameters for the ECC800-Pro
Collector.
Set this parameter to the address set on the device.
on the toolbar to save the device information.
6.5.1.4 Setting RS485 Parameters for the ECC800-Pro
You have the operation rights for Access Control Management and Planning
Configuration.
Copyright © Huawei Technologies Co., Ltd.
Table
Toggle Switch 1
OFF
ON
OFF
ON
6 Adding Devices
6-40.
Toggle Switch 2
OFF
OFF
ON
ON
Collector.
258

Hide quick links:

Advertisement

Table of Contents
loading