iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
Prerequisites
Context
If the smart cooling product is connected over Modbus-TCP, set parameters by
referring to this section.
This section uses FusionCol8000-E400 V100R021C10 as an example.
Procedure
Step 1 Tap Settings on the FusionCol8000-E400 home screen.
Step 2 Enter the user name and password of an administrator.
Step 3 Choose Comm Settings > Modbus Settings and set Modbus-TCP parameters by
referring to
After the Encryption operation CBC parameter is set, the system automatically
restarts. Exercise caution when performing this operation.
Figure 6-40 Warning dialog box
Issue 02 (2021-05-12)
You have obtained the IP address, subnet mask, and default gateway
information planned for the smart cooling product.
The smart cooling product is powered on.
NO TE
The preset user name and password are respectively admin and 000001. To ensure access
security, change the password upon the first login.
Table
6-9.
NO TE
The encryption mode must be the same as it on the NMS.
WARNING
Copyright © Huawei Technologies Co., Ltd.
6 Adding Devices
189