Application; Setting Guidelines; Signal Matrix For Binary Inputs Smbi; Signal Matrix For Binary Outputs Smbo - ABB RELION 670 Series Applications Manual

Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 504 152-UEN B
22.7.2

Application

Global base values function (GBASVAL) is used to provide global values, common for all
applicable functions within the IED. One set of global values consists of values for current,
voltage and apparent power and it is possible to have twelve different sets.
This is an advantage since all applicable functions in the IED use a single source of base values.
This facilitates consistency throughout the IED and also facilitates a single point for updating
values when necessary.
Each applicable function in the IED has a parameter,
twelve sets of GBASVAL functions.
22.7.3

Setting guidelines

UBase : Phase-to-phase voltage value to be used as a base value for applicable functions
throughout the IED.
IBase : Phase current value to be used as a base value for applicable functions throughout the
IED.
SBase : Standard apparent power value to be used as a base value for applicable functions
throughout the IED, typically
22.8

Signal matrix for binary inputs SMBI

22.8.1
Application
The Signal matrix for binary inputs function SMBI is used within the Application Configuration
tool in direct relation with the Signal Matrix tool. SMBI represents the way binary inputs are
brought in for one IED configuration.
22.8.2
Setting guidelines
There are no setting parameters for the Signal matrix for binary inputs SMBI available to the
user in Parameter Setting tool. However, the user shall give a name to SMBI instance and the
SMBI inputs, directly in the Application Configuration tool. These names will define SMBI
function in the Signal Matrix tool. The user defined name for the input or output signal will also
appear on the respective output or input signal.
22.9

Signal matrix for binary outputs SMBO

22.9.1
Application
The Signal matrix for binary outputs function SMBO is used within the Application
Configuration tool in direct relation with the Signal Matrix tool. SMBO represents the way
binary outputs are sent from one IED configuration.
Application manual
SBase =√3· UBase · IBase .
GUID-D58ECA9A-9771-443D-BF84-8EF582A346BF v4
GlobalBaseSel , defining one out of the
GUID-E3F5D754-BD17-4729-895B-957A09C2AC75 v3
Section 22
Basic IED functions
SEMOD55793-1 v2
M15310-3 v2
M15312-3 v3
SEMOD55215-1 v2
SEMOD55213-5 v4
705

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret670