Gas Medium Supervision Ssimg; Identification; Application; Liquid Medium Supervision Ssiml - ABB RELION 670 Series Applications Manual

Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 504 152-UEN B
Table 65: General settings parameters for the Measurement function
Setting
Operation
PowAmpFact
PowAngComp
Mode
k
UGenZeroDb
IGenZeroDb
UBase (set in
Global base)
IBase (set in
Global base)
17.2

Gas medium supervision SSIMG

17.2.1

Identification

Function description
Gas medium supervision
17.2.2

Application

Gas medium supervision (SSIMG) is used for monitoring the circuit breaker condition. Proper
arc extinction by the compressed gas in the circuit breaker is very important. When the
pressure becomes too low compared to the required value, the circuit breaker operation shall
be blocked to minimize the risk of internal failure. Binary information based on the gas
pressure in the circuit breaker is used as an input signal to the function. The function
generates alarms based on the received information.
17.3

Liquid medium supervision SSIML

17.3.1
Identification
Function description
Liquid medium supervision
Application manual
Short description
Operation Off/On
Amplitude factor to scale
power calculations
Angle compensation for phase
shift between measured I & U
Selection of measured current
and voltage
Low pass filter coefficient for
power measurement, U and I
Zero point clamping in % of
Ubase
Zero point clamping in % of
Ibase
Base setting for voltage level
in kV
Base setting for current level
in A
IEC 61850
identification
SSIMG
IEC 61850
identification
SSIML
Selected
Comment
value
On
Function must be
1.000
Typically no scaling is required
0.0
Typically no angle compensation is required.
As well here required direction of P & Q
measurement is towards protected object (as
per IED internal default direction)
Arone
Generator VTs are connected between phases
(V-connected)
0.00
Typically no additional filtering is required
25%
Set minimum voltage level to 25%
3
Set minimum current level to 3%
15,65
Set generator rated phase-to-phase voltage
3690
Set generator rated current
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
63
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
71
Section 17
Monitoring
On
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v3
GUID-A840E38C-CC42-4995-A569-A6092DDB81B2 v5
GUID-37669E94-4830-4C96-8A67-09600F847F23 v3
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v2