A.2.2
Acceptance test STO (basic functions)
Procedure
To perform an acceptance test of the STO function as part of the basic functions, proceed as
follows:
1.
2.
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
The converter is ready
•
The converter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
•
STO is not active (r9773.1 = 0).
Switch on motor
2.1.
Enter a speed setpoint ≠ 0.
2.2.
Switch on the motor (ON command).
2.3.
Check that the correct motor is running.
A.2 Acceptance tests for the safety functions
Appendix
Status
505