4.1
Restoring the factory setting
There are cases where something goes wrong when commissioning a drive system e.g.:
● The line voltage was interrupted during commissioning and you were not able to
● You got confused when setting the parameters and you can no longer understand the
● You don't know whether the inverter was already operational
In cases such as these, reset the inverter to the factory settings.
Restoring the factory setting with STARTER or BOP-2
This function resets the settings in the inverter to the factory settings.
Note
The communication settings and the settings of the motor standard (IEC/NEMA) are retained
even after restoring the factory setting.
Table 4- 1
STARTER
1. Go online with STARTER
2. In STARTER, click on the button
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
complete commissioning.
individual settings that you made.
Procedure
BOP-2
1. In the "Options" menu, select the
"DRVRESET" entry
.
2. Confirm the reset using the OK key
Commissioning
4.1 Restoring the factory setting
55