Commissioning

5.2 Restoring the factory settings

Users can access the inverter parameters via the following interfaces
Figure 5-1
5.2
Restoring the factory settings
If nothing else works, restore the factory settings!
You can restore the factory settings using parameter P0970.
Parameter or
procedure
P0003 = 1
P0010 = 30
P0970 = 1
IOP - select factory
restart from the extras
menu.
STARTER
50
Communications interfaces
Description
User access level
1: Standard level
Commissioning parameter
30: Factory setting, parameter transfer
Restore factory settings
1: Restore the factory parameter settings
The IOP will display a message stating that a factory reset is taking place
and display a progress bar. When completed the display will display a
message that the factory reset has been successfully completed.
Displays a progress bar.