6 Basic Settings

6-10 Multi-function output

6-10-1

Multifunction Output Selection

• Inverter status can be output from output terminals by allocating functions to output terminals [DO1]
and [ROA, ROB]. This section describes seven types of primary functions. For details on other func-
tions, refer to 8-2 Multifunction Input/Output Functions List on page 8-23.
Parameter No.
3005Hex-15Hex/
3005Hex-1CHex
3051Hex-0AHex
3051Hex-0EHex
3051Hex-0BHex
3051Hex-0FHex
• Set this at Output Terminal [DO1] Function Selection (3005Hex-15Hex) and Output Terminal [ROA,
ROB] Function Selection (3005Hex-1CHex).
• An NO contact output can be changed to an NC contact output by setting data in which 1000 is add-
ed to the set data, and, as a result, the operations of set signals are reversed.
• Each multifunction output terminal can be allocated with the ON/OFF delay time independently.
• The output terminal [DO1] is open collector output, and the output terminal [ROA, ROB] is relay out-
put.
• The following functions have an OFF delay time of 0.1 s even if the OFF delay time is not set. When
these functions are allocated to output terminals, the OFF delay becomes the time obtained by add-
ing 0.1 s to Output Terminal [DO1] OFF Delay Time (3051Hex-0BHex) and Output Terminal [ROA,
ROB] OFF Delay Time (3051Hex-0FHex).
Inverter output limited (5: IOL) terminal, Electronic thermal warning (7: THM) terminal, Overload pre-
vention control in progress (36: OLP) terminal, Overload early warning 2 (37: OL2) terminal, Over-
load early warning (38: OL) terminal, Low current signal (41: LOC) terminal, PID deviation excessive
(42: OD) terminal, PID wakeup timer stopped (44: PID-STP) terminal, Overtorque (46: OTQ) termi-
nal, Thermistor detection (56: MOH) terminal
6-60
Function name
Output Terminal [DO1] Function
Selection/Output Terminal
[ROA, ROB] Function Selection
Output Terminal [DO1] ON De-
lay Time
Output Terminal [ROA, ROB]
ON Delay Time
Output Terminal [DO1] OFF De-
lay Time
Output Terminal [ROA, ROB]
OFF Delay Time
Data
Table below or, refer to
8-2 Multifunction Input/
Output Functions List on
page 8-23.
0.0 to 100.0
0.0 to 100.0
M1 Series EtherCAT Type User's Manual (I670)
Default data
Unit
-
-
0.0
s
0.0
s