5-10 Multi-function Output Settings

5-10-1 Multi-function Output Selection

• Use this function to allocate the functions listed below to the multi-function output P1 to P5 terminals
and the multi-function relay output (MA, MB) terminals.
• The multi-function output P1 to P5 terminals are for open collector output and the multi-function relay
output (MA, MB) terminals are for relay output.
• Set the desired function in the Multi-function Output P1 Selection (C021 to C025) and the
Multi-function Relay Output (MA, MB) Function Selection (C026).
• If the alarm code output function is enabled in Alarm Code Selection (C062) (Alarm Code Output
(AC0 to AC3) on page 7-130), some multi-function output settings to select alarm code output are
disabled.
When C062 is set to 01 (3 bits), the output terminals P1 to P3 are used for alarm code output; when
C062 is set to 02 (4 bits), the output terminals P1 to P4 are used for alarm code output.
• This section describes seven types of primary functions. For other functions, refer to 7-5
Multi-function Terminal Functions (Group C) on page 7-108.
Parameter
No.
C021 to C025,
C026
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Data
Function name
00
RUN: During RUN signal
01
FA1: Constant speed arrival signal Frequency arrival signal
05
AL: Alarm signal
21
ZS: 0-Hz detection signal
50
IRDY: Operation ready
51
FWR: Forward run signal
52
RVR: Reverse run signal
5 Basic Settings
Reference item
During RUN signal
Alarm signal
0-Hz detection signal
Operation ready signal
Forward run signal
Reverse run signal
Page
5
5-61
5-61
5-62
5-63
5-63
5-64
5-64
5 - 59