when the frequency is other than zero, the frequency calculated at that point will be output. Be-
cause of this, if the baseblock is cleared during deceleration while the motor is free running, a
large discrepancy between the motor speed at that moment and the Inverter output frequency
may result in a main circuit overvoltage (OV) or overcurrent (OC).
H Speed Search (Set Value: 14, 15)
The speed search function is provided for smooth restarting without stopping a free running motor. Use
it when switching the motor from commercial power supply operation to Inverter operation, when start-
ing with the Inverter a motor turned by external force, etc.
The speed search function searches for the present motor frequency, from high frequency to low. When
the motor's rotation speed is detected, it is accelerated from that frequency to the frequency reference
according to the acceleration/deceleration time setting.
Speed Search Function
Forward (reverse)
RUN command
Speed Search command
Output frequency
High-speed frequency
or set frequency
(frequency reference)
Minimum base block time (0.5 s)

5-9-2 Multi-function Output

The 3G3JV incorporates two multi-function output terminals (MA and MB).
Output from these terminals has a variety of functions according to the application.
H Selecting the Multi-function Output (n40)
n40
Multi-function Output (MA/MB and MC)
Setting
0 to 7, 10 to 17
range
(see note)
Note Do not set values outside the above setting ranges.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
ON
0.5 s min.
Speed search operation
Unit of
1
setting
ON
Changes during
operation
Default setting