Electronic Thermal Overload Function; Multi-Function Analog Output Monitor - Omron SYSDRIVE 3G3XV-EV2 Series Operation Manual

Table of Contents

Advertisement

Description of Functions and Constants
2-8-8

Electronic Thermal Overload Function

Item name
Motor type
Motor rated current
2-8-9

Multi-function Analog Output Monitor

Item name
Output monitor selection
Constant to be set
No. 18
No. 19
Motor output current is monitored by the Inverter's built-in elec-
tronic thermal overload function to prevent Inverter exclusive-use
motors or standard motors from overloading.
It is not necessary to mount an thermal overload relay externally.
However, to connect several motors to one Inverter, a thermal
overload relay must be inserted for each motor. It is necessary to
reduce carrier frequency according to the wiring distance between
the Inverter and motor when thermal overload relays are inserted.
For details, refer to the precautions on wiring described in 1-4 Wir-
ing .
No. 19 = Motor rated current value
Set the motor rated current value according to the
value on the motor nameplate.
No. 18 = xx00
st
1
digit
0: Electronic thermal overload function enabled
1: Electronic thermal overload function disabled
nd
2
digit
0: Standard motor
1: Exclusive-use motor
Electronic thermal protection can be disabled by setting "No. 18 =
xxx1."
Constant to be set
No. 21
Output frequency or motor current can be monitored. (Standard
function)
No. 21 = xx0x
nd
2
digit
0: Output frequency is monitored.
1: Motor current is monitored.
Analog output monitor gain can be set to No. 45.
Section 2-8
Factory preset
0000
1.9 A (for A2004)
Factory preset
0000
49