Omron M1 Series User Manual page 771

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

(6) Short-circuit detection was
activated by the built-in braking
transistor (22 kW or less).
(7) The inverter malfunctioned
due to noise.
Attached in-
None
formation
Precautions/
None
Remarks
M1 Series EtherCAT Type User's Manual (I670)
Check if the braking resistor con-
nection terminals (P(+) and DB)
are short-circuited. Check if the
resistance value of the connect-
ed braking resistor is extremely
low.
→ Connect an appropriate brak-
ing resistor.
Check the measures against
noise (grounding condition, con-
trol/main circuit wiring and instal-
lation).
→ Take measures against noise.
→ Enable the function of Auto-
reset Count (3008-05 hex).
→ Connect a surge absorber to
the coil, solenoid, etc. of the
electromagnetic contactor, which
is the noise source.
Appendices
Connect an appropriate braking
resistor.
Excessive noise may be generat-
ed around the inverter. Consider
taking measures against noise.
A-225