UP
OFF
ON
In the inverter, the PID control values set by the UP/DOWN control are maintained internally, and
when the operation is resumed (including when the power is turned ON), the control is started from the
previous PID command value.
When analog input is applied to the PID command value, the following gains, biases, filters and offsets
are applicable.
Input ter-
Input range
minal
0 to +10V,
AI1
-10 to +10V
The following processing is performed during polarity selection 3006Hex-24Hex.
3006Hex-24Hex: Set the input range of the AI1 terminal.
3006Hex-24Hex
0
1
An example of PID process control is shown below.
The value after conversion becomes 0% to 100% or more.
100%
Gain
Bias
base point
0%
-10%
Bias
A point
An example of dancer control is shown below.
M1 Series EtherCAT Type User's Manual (I670)
DWN
The command values of PID control decrease according to the change rate
ON
from 0.1%/0.1 s to 1%/0.1 s.
ON
The current command values of PID control are retained.
Bias
Base
Bias
point
3006Hex-
3006Hex-
38Hex
39Hex
-10 to +10V,
0 to +10V (A negative voltage is considered as 0V.)
Used for unipolar
B point
Analog
input
Gain
100%
base point
Operation
Gain
Polarity
selection
(Range
Base
Gain
selec-
point
tion)
3006Hex-
3006Hex-
3006Hex-
21Hex
23Hex
24Hex
Terminal input specifications
Used for bipolar
The value after conversion becomes -100% to 100% or more.
100%
Gain
Bias
base point
0%
-10%
base point
Bias
A point
8 Other Functions
Filter
Offset
3006Hex-
3006Hex-
22Hex
20Hex
B point
Analog
input
Gain
100%
8-115
8