Omron M1 Series User Manual page 819

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

Event name
Abnormal Setting Related to the PG Option Card
Meaning
The pulse generator wiring is broken in the circuit.
Source
EtherCAT Master Function Mod-
ule
Error attrib-
Level
utes
Effects
User program
Indicators
EtherCAT NET RUN
---
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
(1) The wiring between the pulse
generator and the pulse input ter-
minal is disconnected.
(2) Strong ambient noise was re-
ceived.
Attached in-
None
formation
Precautions/
None
Remarks
M1 Series EtherCAT Type User's Manual (I670)
Source details Slave
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
None
Correction
Check if the pulse generator is
correctly connected and there is
no disconnection.
→ Check if the pulse generator is
correctly connected. Or securely
connect the wiring to the terminal
block.
→ Check if the sheath is not
caught in the connector.
→ Replace it with wire that is not
broken.
Check the measures against
noise (grounding condition, sig-
nal line or communications cable/
main circuit wiring installation
method, etc.).
→ Take measures against noise.
→ Install the main circuit wiring
as far as possible from the con-
trol circuit wiring.
Event code
38A30000 hex
Detection tim-
ing
Error reset
Log category
Motor stops.
EtherCAT LINK/ACT
---
Name
None
Prevention
None
Excessive noise may be generat-
ed around the inverter. Consider
taking measures against noise.
Appendices
Continuously
System log
A
A-273

Hide quick links:

Advertisement

Table of Contents

Troubleshooting