Advertisement

Event name
Step-out Detection/Magnetic Pole Position Detec-
tion Error during Startup
Meaning
Step-out of the PM motor was detected. Magnetic pole position detection failed at startup.
Source
EtherCAT Master Function Mod-
ule
Error attrib-
Level
utes
Effects
User program
Indicators
EtherCAT NET RUN
---
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
(1) The characteristics of the mo-
tor are different.
(2) The magnetic pole position
detection method is not appropri-
ate.
(3) The value of 1st Starting
frequency 1 Holding time
(3004-19 hex) is insufficient.
M1 Series EtherCAT Type User's Manual (I670)
Source details Slave
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
None
Correction
Confirm that the settings of 1st
Base Frequency (3004-05 hex),
1st rated voltage at base
frequency (3004-06 hex), and
motor parameters (3007-02 to 04
hex, 3007-3D to 41 hex) are con-
sistent with the motor constants.
→ Perform auto-tuning.
Confirm that the magnetic pole
position detection method is suit-
able for the motor type.
→ Set 1st PM motor drive
magnetic pole position
detection mode (3007-1F hex)
according to the motor type.
Check if 1st Starting frequency
1 Holding time (3004-19 hex) is
set optimally when 1st PM
motor drive magnetic pole
position detection mode
(3007-1F hex) is set to 0 or 3.
→ Set a time that allows for at
least one rotation of the motor.
F24* ≥ P01* / 2 / F23* (P01*:
Number of poles, F23*: Starting
frequency)
F24 = 1st Starting frequency 1
Holding time (3004-19 hex)
F23 = 1st Starting Frequency
(3004-18 hex)
P01 = 1st Motor Pole Number
(3007-02 hex)
Event code
38A00000 hex
Detection tim-
ing
Error reset
Log category
Motor stops.
EtherCAT LINK/ACT
---
Name
None
Prevention
Set the motor constant parame-
ters according to the motor char-
acteristics and perform auto-tun-
ing.
Set 1st PM motor drive
magnetic pole position
detection mode (3007-1F hex)
appropriately.
Set 1st Starting frequency 1
Holding time (3004-19 hex) to
an appropriate value.
Appendices
Continuously
System log
A
A-265