Omron M1 Series User Manual page 798

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

Appendices
Event name
1st Motor Overload Protection
Meaning
Motor 1 is overloaded.
Source
EtherCAT Master Function Mod-
ule
Error attrib-
Level
utes
Effects
User program
Indicators
EtherCAT NET RUN
---
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
(1) The characteristics of the
electronic thermal and the over-
load characteristics of the motor
do not match.
(2) The operation level of the
electronic thermal is not appro-
priate.
(3) The acceleration/deceleration
time is short.
(4) The load is large.
A-252
Source details Slave
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
None
Correction
Check the motor characteristics.
→ Review the values of 1st
motor electronic thermal
overload protection mode
(3004-0B hex) and 1st motor
electronic thermal time
constant (3004-0D hex).
→ Use an external thermal relay.
Recheck the motor's continuous
allowable current.
→ Review and change the value
of 1st Motor Electronic
Thermal Level (3004-0C hex).
Recalculate the required acceler-
ation/deceleration torque and ac-
celeration/deceleration time
based on the load's moment of
inertia and acceleration/decelera-
tion time.
→ Increase the values of 1st
Acceleration Time 1 (3004-08
hex), 1st Acceleration Time 2
(3005-0D hex), 1st Deceleration
Time 1 (3004-09 hex), and 1st
Deceleration Time 2 (3005-0E
hex).
Measure the output current.
→ Reduce the load. (Use 1st
Overload Early Warning
Detection Level (3005-26 hex)
and Overload early warning 2
Level (3005-23 hex) to reduce
the load before overloading oc-
curs. In winter, the load may be-
come larger.)
Event code
08860000 hex
Detection tim-
ing
Error reset
Log category
Motor stops.
EtherCAT LINK/ACT
---
Name
None
Prevention
Set the parameters according to
the motor characteristics.
Set the electronic thermal's oper-
ation level appropriately.
Set the acceleration/deceleration
time as long as possible to re-
duce the load. Or set a longer
stop time to reduce the load.
Select a motor and an inverter
according to the load.
M1 Series EtherCAT Type User's Manual (I670)