Omron M1 Series User Manual page 279

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

Parameter
No.
3014Hex-1
Speed Deviation Error Processing Se-
8Hex
lection
3014Hex-2
Speed Limit 1 in Forward
1Hex
3014Hex-2
Speed Limit 2 in Reverse
2Hex
3014Hex-2
Over Speed Detection Level
4Hex
3005Hex-0
2Hex to
3005Hex-0
6Hex,
Input Terminal [DI1] to [DI7] Function
3005Hex-6
Selection
3Hex,
3005Hex-6
4Hex
 Overspeed error detection
If the output frequency exceeds the overspeed protection level, the inverter detects the overspeed
protection alarm (alarm code: 1B) and shuts off (trips) inverter output.
• Conditions that cause an overspeed protection alarm
Over Speed Detection Level (3014Hex-24Hex) = 999 
<Forward rota-
tion side>
<Reverse rota-
tion side>
Over Speed Detection Level (3014Hex-24Hex) = Other than 999
Overspeed protection level = 1st Maximum Output Frequency (3004Hex-04Hex)/2nd Maximum
Output Frequency (3009Hex-02Hex) × Over Speed Detection Level (3014Hex-24Hex) (%)
 Speed mismatch/excessive speed deviation
If the state where the difference between the frequency reference and the actual frequency ex-
ceeds the set value of Speed Agreement / Speed Deviation Error Hysteresis Width
(3014Hex-16Hex) continues for Speed Agreement / Speed Deviation Error Detection Timer
(3014Hex-17Hex), this state is judged to be a speed mismatch/excessive speed deviation, post-de-
tection processing is performed according to the setting of Speed Deviation Error Processing Se-
lection (3014Hex-18Hex).
M1 Series EtherCAT Type User's Manual (I670)
Function name
Overspeed protection level = 1st Maximum Output Frequency (3004Hex-04Hex)/2nd
Maximum Output Frequency (3009Hex-02Hex) × Speed Limit 1 in Forward
(3014Hex-21Hex) (%) × 120 (%) 
Overspeed protection level = 1st Maximum Output Frequency (3004Hex-04Hex)/2nd
Maximum Output Frequency (3009Hex-02Hex) × Speed Limit 2 in Reverse
(3014Hex-22Hex) (%) × 120 (%)
7 Vector Control and Applied Functions
Data
0: Continue to run 1
1: Stop with alarm 1
2: Stop with alarm 2
3: Continue to run 2
4: Stop with alarm 3
5: Stop with alarm 4
0 to 110
0 to 110
0 to 120,
999: Depend on
3014Hex-21Hex,
3014Hex-22Hex
71: DSAG (Speed agree-
ment)
76: DSE (Excessive
speed deviation)
Default da-
Unit
ta
2
-
100
%
100
%
999
%
-
-
7-13
7

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents