Omron M1 Series User Manual page 779

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

(3) The deceleration time is short
for the load's moment of inertia.
(4) The acceleration time is
short.
M1 Series EtherCAT Type User's Manual (I670)
Recalculate the deceleration tor-
que based on the load's moment
of inertia and deceleration time.
→ Increase the values of 1st
Deceleration Time 1 (3004-09
hex), 2nd Deceleration Time 1
(3005-0C hex), 1st Deceleration
Time 2 (3005-0E hex), and 2nd
Deceleration Time 2 (3005-10
hex).
→ Enable the function of Anti-
regenerative control Mode
selection (3008-46 hex) or
Deceleration characteristics
(3008-48 hex).
→ Enable the functions of
Torque Limit 1 (Four-quadrant
Mode Forward Power Running)
(3004-29 hex), Torque Limit 2
(Four-quadrant Mode Reverse
Regeneration) (3004-2A hex),
Torque Limit 3 (Four-quadrant
Mode Reverse Power Running)
(3005-11 hex), and Torque Limit
4 (Four-quadrant Mode
Forward Regeneration)
(3005-12 hex).
→ Set the value of 1st rated
voltage at base frequency
(3004-06 hex) to 0 to improve the
braking performance.
→ Consider using a braking re-
sistor.
Check if an overvoltage alarm
occurs at the end of quick accel-
eration.
→ Increase the values of 1st
Acceleration Time 1 (3004-08
hex), 2nd Acceleration Time 1
(3005-0B hex), 1st Acceleration
Time 2 (3005-0D hex), and 2nd
Acceleration Time 2 (3005-0F
hex).
→ Use Acceleration/
Deceleration Pattern Selection
(3008-08 hex).
→ Consider using a braking re-
sistor.
Appendices
Set an appropriate deceleration
time for the load's moment of in-
ertia.
Set the acceleration/deceleration
time as long as possible to re-
duce the load. Or set a longer
stop time to reduce the load.
A-233
A