6 Basic Settings
6-5

Frequency Reference

6-5-1

Frequency Reference Selection

• Select the input method for the frequency reference.
Parameter
No.
3004Hex-0
1st Frequency Reference
2Hex/
Selection/2nd Frequency
3006Hex-1
Reference Selection
FHex
3002Hex-0
Operation command
7Hex
Related function
*1.
To enable switching to the 1st and 2nd control, allocate "12: SET (2nd control)" to either of input terminal
[DI1] to [DI7].
The frequency reference method for data selected at 1st Frequency Reference Selection
(3004Hex-02Hex) and 2nd Frequency Reference Selection (3006Hex-1FHex) is as follows.
Data
1
7
10
12
13
14
• The forced terminal block function are given priority over the frequency reference selected at Fre-
quency Reference Selection (3004Hex-02Hex/3006Hex-1FHex). For details, refer to 8-6-3 STO
Function by Safety Input Signal on page 8-62.
Command Using Analog Voltage Input (Frequency Reference Se-
lection (3004Hex-02Hex/3006Hex-1FHex) = "1")
• Analog input can adjust the input signal by gain and bias. (Refer to 8-3-2 Analog Input Adjustment
Function on page 8-34.)
• Behavior when the analog signal is disconnected can be set at analog reference loss detection.
 Analog Reference Loss Detection
When the analog frequency reference falls to 10% or lower of the frequency reference for 400 ms,
the wiring of the analog frequency reference is judged to have become disconnected, operation is
6-24
Function name
1: Analog Valtage Input (Input Termi-
nal[AI1])
7: UP/DOWN control
10: Pattern operation
*1
12: Pulse train input
13: Calculation result
15: EtherCAT
Bit1: REV
Bit0: FWD
Input Terminal [DI1] to [DI7] Function Selection (3005Hex-02Hex to
3005Hex-06Hex, 3005Hex-63Hex, 3005Hex-64Hex)
Sets the frequency reference via the analog voltage input (input terminal [AI1]).
Sets the frequency reference via the UP and DOWN terminals.
Sets the frequency reference via Pattern Operation Function Selection.
Sets the frequency reference via pulse train input.
The result of calculation of the frequency calculation function is set as the frequen-
cy reference.
Sets the frequency reference via EtherCAT communication.
Data
Frequency reference method
M1 Series EtherCAT Type User's Manual (I670)
Default da-
Unit
ta
15
-
0
-