Trip Retry Operation

This function is used to set the operation selection to restart during overvoltage or overcurrent.
Parameter No.
301FHex-28Hex
3008Hex-05Hex
3008Hex-06Hex
3005Hex-15Hex/
3005Hex-1CHex
Overvoltage/Overcurrent Restart Function Selection
(301FHex-28Hex)
301FHex-28Hex
data
0: Trip
4: Restart based on
pull-in frequency
*1.
With auto search is Enable auto search for idling motor speed at starting "STM" is ON, or
3008Hex-0AHex(3014Hex-44Hex) = 1 or 2.
When a motor control method with speed sensor is selected, restart is performed from the motor speed de-
tected by the speed sensor. In the case of a motor control method without speed sensor, restart is per-
formed from the estimated speed.
8-50
Power failure
Power restoration
Function name
Overvoltage/Overcurrent Re-
start Function Selection
Retry Count at Trip 
Retry Standby Time at Trip
Output Terminal [DO1] Function
Selection/Output Terminal
[ROA, ROB] Function Selection
Without auto search
An alarm is output when an overvoltage or overcurrent is detected, the inverter output is
cut off, and the motor falls in a free-run state.
If an overvoltage or overcurrent is detected, the inverter output is cut off, and the motor
falls in a free-run state.
During recovery from overvoltage or over-
current, restart is performed from the pull-
in frequency. Select the pull-in frequency at
Starting Frequency Selection at Frequency
Pull-in Restart (301FHex-35Hex).
Continuous Running Voltage Level (3008Hex-10Hex)
Continuous Running Voltage Level (3008Hex-10Hex + 10V)
Undervoltage level
Data
0: Trip immediately
4: Restart at the frequency
selected by 301FHex-35Hex
0: Disable
1 to 20: Number of retries
0.5 to 20.0
26: TRY (Auto-resetting)
Operation details
With auto search
During recovery from overvoltage or over-
current, auto search is performed, the mo-
tor speed is estimated, and restart is per-
formed from the frequency.
M1 Series EtherCAT Type User's Manual (I670)
Default data
Unit
0
-
0
-
5
s
-
-