8 Other Functions
Set frequency (1) + 3005Hex-1FHex
Set frequency (1) - 3005Hex-1FHex
Set frequency (2) + 3005Hex-1FHex
Set frequency (2) - 3005Hex-1FHex
Frequency arrival signal 1
(constant speed) "FAR1"
Frequency arrival signal 2 "FAR2"
Over Set Frequency Arrival Signal (3005Hex-15Hex,
3005Hex-1CHex = 2: FDT1, 31:FDT2)
An ON signal is output when the output frequency becomes equal to or higher than Frequency Detec-
tion Level (3005Hex-20Hex/3005Hex-25Hex), and the signal is turned OFF when the frequency falls
below Frequency Detection Hysteresis Width (3005Hex-21Hex).
Name
Over set frequency ar-
rival signal 1
Over set frequency ar-
rival signal 2
Over set frequency arrival signal 1 "FDT1"
Over set frequency arrival signal 2 "FDT2"
Set-Frequency-Only Arrival Signal (3005Hex-15Hex,
3005Hex-1CHex = 183: FDT3, 185: FDT4)
An ON signal is output when the output frequency is within the range of Frequency Detection Level
(3005Hex-20Hex/3005Hex-25Hex), and the signal is turned OFF when the output frequency is out of
range.
8-80
Frequency setting
Set frequency (1)
Set frequency (2)
Frequency Arrival 2 ON Timer
(3005Hex-1EHex)
3005Hex-15Hex,
Output signal
3005Hex-1CHex
allocated data
FDT1
FDT2
Output frequency
Frequency settings changed
Output frequency
ON
Frequency
Arrival 2 ON
Timer
(3005Hex-
ON
1EHex)
Operation level
Range: 0.0 to
500.0Hz
2
3005Hex-20Hex
31
3005Hex-25Hex
Set frequency
ON
M1 Series EtherCAT Type User's Manual (I670)
ON
ON
Hysteresis width
Range: 0.0 to
500.0Hz
3005Hex-21Hex
Operation level
(3005Hex-20Hex/3005Hex-25Hex)
Frequency Detection Hysteresis Width
(FDT1/ FDT2) (3005Hex-21Hex)
Cancellation level
Time