Parameter
No.
3014Hex-4
Speed Control Slip Frequency
7Hex
Limit
V/f control with speed feedback slip compensation proportional gain
At first, adjust the proportional gain for speed feedback control.
• Check and gradually increase the set value of PG feedback value (3017Hex-11Hex).
• While checking the PG feedback value (3017Hex-11Hex), increase the value within the range
where the motor speed is stable.
• If the motor speed fluctuates or the motor vibrates wildly, decrease the set value until it becomes
stable.
• When adjusting the response if the load is actually activated, increase the set value to improve
response, or decrease the set value to make it stable.
V/f control with speed feedback slip compensation integral time
Next, adjust the integral time for speed feedback control.
• Check and gradually decrease the set value of PG feedback value (3017Hex-11Hex).
• Decrease the value in the PG feedback value (3017Hex-11Hex) until it matches the reference
frequency.
• If the motor speed fluctuates or the motor vibrates wildly, increase the set value until it becomes
stable.
• When adjusting the response if the load is actually activated, decrease the set value to improve
response, or increase the set value to make it stable.
Speed control limiter
Speed Control Slip Frequency Limit (3014Hex-47Hex) is the limiter for the slip frequency that is
added to the frequency reference. The maximum frequency is taken to be 100%. Ordinarily, leaving
this setting at 100% causes no problems.
M1 Series EtherCAT Type User's Manual (I670)
Function name
IM V/f control with speed sensor
IM Dynamic torque vector control with speed sensor
Frequency
reference
Speed
[3014Hex-04Hex],
detection value
([3009Hex-2EHex],
[3013Hex-2EHex],
[300CHex-2EHex])
7 Vector Control and Applied Functions
Data
0.00 to 100.00
[3014Hex-47Hex]
Slip
frequency
calculation
[3014Hex-47Hex]
[3014Hex-05Hex],
([3009Hex-2FHex],
[3013Hex-2FHex],
[300CHex-2FHex])
Default da-
Unit
ta
100.00
%
Output
frequency
7-15
7