5-11 Multi-function Analog Output and Pulse Monitor
Output
The 3G3MV Inverter incorporates a multi-function analog output terminal
(AM-AC). A parameter setting makes it possible to output pulse monitor
signals from these terminals. Make the necessary settings in these termi-
nals according to the application.
5-11-1 Setting the Multi-function Analog Output (n065
through n067)
·By setting n065 for multi-function analog output type selection to 0 for analog voltage
output, analog monitoring is possible through the multi-function analog output termi-
nal.
·A monitoring item is set in n066 (multi-function analog output selection). Six items
including the output frequency and current are available.
·Set the analog output characteristics in n067 (multi-function analog output gain).
Multi-function Analog Output
n065
Type Selection
Setting
0, 1
range
Set Values
Value
0
Analog voltage output (with monitoring item set in n066)
1
Pulse train output (according to output frequency set in n150)
Multi-function Analog Output
n066
Setting
0 to 5
range
Set Values
Value
0
Output frequency (Reference: 10-V output at max. frequency)
1
Output current (Reference: 10-V output at rated inverter output current)
2
Main circuit DC voltage (Reference: 10-V output at 400 VDC for 200-V
models and 800 VDC for 400-V models)
3
Vector operation torque monitor (Reference: 10-V output at rated motor
torque)
Register 0141
Hex
Unit of
1
setting
Description
Register 0142
Hex
Unit of
1
setting
Description
Chapter 5
Changes during
operation
Default setting
Changes during
operation
Default setting
No
0
No
0
5-41