Omron M1 Series User Manual page 675

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

Sub-
Pa-
Index
index
rame-
(hex)
(hex)
ter No.
3C
C59
Input Terminal
[AI1] Analog In-
put Adjustment
Maximum Scale
3D
C60
Input Terminal
[AI1] Analog In-
put Adjustment
Minimum Scale
5A
C89
Set-point Factor
Numerator via
Communication
5B
C90
Set-point Factor
Denominator via
Communication
A-4-8
P Group Parameter List (Motor 1 Parameters)
Sub-
Pa-
Index
index
rame-
(hex)
(hex)
ter No.
3007
02
P01
1st Motor Pole
Number
03
P02
1st Motor Ca-
pacity
04
P03
1st Motor Rated
Current
05
P04
1st Auto Tuning
Function Selec-
tion
M1 Series EtherCAT Type User's Manual (I670)
Function name
Monitor or data range
V/f
DTV
SLV
PGV PM SLV PM PGV
-999.00 to 9,990.00
V/f
DTV
SLV
PGV PM SLV PM PGV
-999.00 to 9,990.00
V/f
DTV
SLV
PGV PM SLV PM PGV
-32,768 to 32,767
V/f
DTV
SLV
PGV PM SLV PM PGV
-32,768 to 32,767
Function name
Monitor or data range
V/f
DTV
SLV
PGV PM SLV PM PGV
2 to 128
V/f
DTV
SLV
PGV PM SLV PM PGV
0.01 to 1,000
V/f
DTV
SLV
PGV PM SLV PM PGV
0.00 to 500.0
V/f
DTV
SLV
PGV PM SLV PM PGV
0: Disable
1: Tune the motor parameters while
stopped
2: Tune the motor parameters while
rotating
4: Tune the PM motor magnetic pole
position offset while rotating
5: Tune the motor %R1 and %X
while stopped
Default
data
100
PG V/f PG DTV
0
PG V/f PG DTV
1
PG V/f PG DTV
1
PG V/f PG DTV
Default
data
4
PG V/f PG DTV
5.50
PG V/f PG DTV
21
PG V/f PG DTV
0
PG V/f PG DTV
Appendices
Set-
ting
PDO
dur-
Unit
map
ing
RUN
---
---
Possible
---
---
Possible
---
Possible
---
Possible
Set-
ting
PDO
dur-
Unit
map
ing
RUN
---
Poles
Possible
---
kW
Possible
---
A
Possible
---
---
Possible
A-129
A

Hide quick links: