Event name
Overcurrent Protection (During Deceleration)
Meaning
Overcurrent occurred during deceleration.
Source
EtherCAT Master Function Mod-
ule
Error attrib-
Level
utes
Effects
User program
Indicators
EtherCAT NET RUN
---
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
(1) The inverter output is short-
circuited.
(2) There is a ground fault on the
inverter output.
M1 Series EtherCAT Type User's Manual (I670)
Source details Slave
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
None
Correction
Disconnect the wires from the in-
verter output terminals (U, V, and
W) and measure the phase-to-
phase resistance of the motor
wires. Check that there are no
wires with extremely low phase-
to-phase resistance.
→ Remove the short-circuit.
(This includes wire, relay termi-
nal, and motor replacement.)
If overcurrent is indicated when
the inverter is operating with the
wires disconnected from the in-
verter output terminals (U, V, and
W)
→ There is a possibility of an in-
verter failure.
Disconnect the wires from the in-
verter output terminals (U, V, and
W) and perform a megger test.
→ Remove the ground fault.
(This includes wire, relay termi-
nal, and motor replacement.)
If overcurrent is indicated when
the inverter is operating with the
wires disconnected from the in-
verter output terminals (U, V, and
W)
→ There is a possibility of an in-
verter failure.
Event code
087A0000 hex
Detection tim-
ing
Error reset
Log category
Motor stops.
EtherCAT LINK/ACT
---
Name
None
Prevention
Confirm that the motor cables
are not broken and connect them
correctly.
Confirm that the motor cables
are not broken and connect them
correctly.
Appendices
Continuously
System log
A
A-223