Motor Electronic Thermal Warning
Use this function to output a warning signal before the motor electronic thermal function executes an
overload protection. The electronic thermal warning operates at or above the current value set in the
Overload early warning 2 Level (OL2) (3005Hex-23Hex). Generally, set to around 80% to 90% of the
current value of the Motor Electronic Thermal Level (3004Hex-0CHex/3009Hex-08Hex). The tempera-
ture characteristics of the motor are set in Motor Electronic Thermal Characteristic Selection
(3004Hex-0BHex/3009Hex-07Hex) or Motor Electronic Thermal Time Constant (3004Hex-0DHex/
3009Hex-09Hex).
Parameter No.
3005Hex-15Hex/
3005Hex-1CHex
3005Hex-23Hex
M1 Series EtherCAT Type User's Manual (I670)
20
15
10
5
0
0
50
(Output current value / Operation level current value) × 100 (%)
Function name
Output Terminal [DO1] Func-
tion Selection/Output Termi-
nal [ROA, ROB] Function Se-
lection
Overload early warning 2
Level (OL2)
Change with 3004Hex-0DHex
3004Hex-0DHex=10
3004Hex-0DHex=5
3004Hex-0DHex=0.5
100
150
200
Data
7: THM (Electronic thermal
warning)
0.00: Disable
0.01 to 176.0
# Setting range from 1%
(HHD) to 200% (ND) of the
rated inverter current.
6 Basic Settings
Default da-
Unit
ta
-
-
21.0
A
6-21
6