Faults/Alarms Trigger Selection / F/A Trigger Sel; Co/Bo: Faults/Alarms Trigger Signal / F/A Trigger Signal - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Notice:
It is not possible to re-parameterize the acknowledge mode for a fault in the following cases:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Acknowledge mode is not permissible for the set fault number.
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = IMMEDIATELY (POWER ON)
--> The acknowledge mode can be changed from IMMEDIATELY to POWER ON.
p2128[0...15]

Faults/alarms trigger selection / F/A trigger sel

All objects
Can be changed: U, T
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Sets the faults/alarms for which a trigger signal should be generated in r2129.0...15.
Dependency:
If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set.
Refer to: r2129
r2129.0...15

CO/BO: Faults/alarms trigger signal / F/A trigger signal

All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Display and BICO output for the trigger signals of the faults/alarms set in p2128[0...15].
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Dependency:
If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set.
Refer to: p2128
Note:
CO: r2129 = 0 --> None of the selected messages has occurred.
CO: r2129 > 0 --> At least one of the selected messages has occurred.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
Trigger signal p2128[0]
Trigger signal p2128[1]
Trigger signal p2128[2]
Trigger signal p2128[3]
Trigger signal p2128[4]
Trigger signal p2128[5]
Trigger signal p2128[6]
Trigger signal p2128[7]
Trigger signal p2128[8]
Trigger signal p2128[9]
Trigger signal p2128[10]
Trigger signal p2128[11]
Trigger signal p2128[12]
Trigger signal p2128[13]
Trigger signal p2128[14]
Trigger signal p2128[15]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8050, 8070
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8070
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
FP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
511