Technology Controller Integral Time / Tec_Ctrl Tn; Bi: Hold Technology Controller Integrator / Tec_Ctr Integ Hold; Ci: Technology Controller Pre-Control Signal / Tec_Ctr Prectr_Sig; Co: Technology Controller Maximum Limiting / Tec_Ctrl Max_Lim - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

p2285

Technology controller integral time / Tec_ctrl Tn

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.000 [s]
Description:
Sets the integral time (I component, integrating time constant) of the technology controller.
Dependency:
Refer to: p2252
Note:
p2285 = 0: The integral time is disabled.
p2286[0...n]

BI: Hold technology controller integrator / Tec_ctr integ hold

VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the signal source to hold the integrator for the technology controller.
p2289[0...n]

CI: Technology controller pre-control signal / Tec_ctr prectr_sig

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the signal source for the pre-control signal of the technology controller.
p2291

CO: Technology controller maximum limiting / Tec_ctrl max_lim

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the maximum limit of the technology controller.
Dependency:
Refer to: p2292
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2292
CO: Technology controller minimum limiting / Tec_ctrl min_lim
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the minimum limit of the technology controller.
Dependency:
Refer to: p2291
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
60.000 [s]
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
200.00 [%]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
541

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents