Bi: Voltage-Controlled Operation Inhibit / U_Ctrl Op Inhib; Co: Dc Link Controller Active Current Setpoint / Vdc I_Act Set; Ci: Dc Link Pre-Control Power (Scaled) / Vdc Prectrl P Scal; Ci: Dc Link Pre-Control Power (Not Scaled) / Vdc Pre-Ctrl P - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

p3513

BI: Voltage-controlled operation inhibit / U_ctrl op inhib

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for disabling DC-link voltage control on the motor side.
r3517

CO: DC link controller active current setpoint / Vdc I_act set

VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
- [Arms]
Description:
Display and connector output for the unlimited setpoint of the active current controller of the DC link voltage control
on the motor side.
p3519[0...3]

CI: DC link pre-control power (scaled) / Vdc prectrl P scal

VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Unsigned32 / FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
-
Description:
Sets the signal source for power pre-control.
Dependency:
Refer to: p3521
Note:
Closed-loop control of the DC link voltage is improved by pre-controlling the power required for the other
components.
A scaled quantity is expected so that the various power reference values (r2004) of the drive objects must be taken
into account. The scaling factors are used to adapt the scaling (p3521).
p3520[0...3]

CI: DC link pre-control power (not scaled) / Vdc pre-ctrl P

VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Unsigned32 / FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
-
Description:
Sets the signal source for power pre-control.
Dependency:
Refer to: p3521
Note:
Closed-loop control of the DC link voltage is improved by pre-controlling the power required for the other modules.
A non-scaled quantity is expected so that the various power reference values (r2004) of the drive objects do not have
to be taken into account. The scaling factors are used to adapt the scaling (p3521).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: 6_2
Scaling: p2002
Max
- [Arms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: r2004
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 7960
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 6220, 7960
Unit selection: p0505
Expert list: 1
Factory setting
- [Arms]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7960
Unit selection: -
Expert list: 1
Factory setting
0
569