r1077
CO: Supplementary setpoint effective / Suppl setpoint eff
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
- [rpm]
Description:
Displays the effective supplementary setpoint. The value shown is the additional setpoint after scaling.
r1078
CO: Total setpoint effective / Total setpoint eff
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
- [rpm]
Description:
Displays the total effective setpoint.
The value indicates the sum of the effective main setpoint and supplementary setpoint.
p1080[0...n]
Minimum speed / n_min
VECTOR_G
Can be changed: C2(1), T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
0.000 [rpm]
Description:
Sets the lowest possible motor speed.
This value is not undershot in operation.
Dependency:
Refer to: p1106
Notice:
The effective minimum speed is formed from p1080 and p1106.
Note:
The parameter value applies for both motor directions.
In exceptional cases, the motor can operate below this value (e.g. when reversing).
p1081
Maximum speed scaling / n_max scal
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
100.00 [%]
Description:
Sets the scaling for the maximum speed (p1082).
For a higher-level speed control, this scaling allows the maximum speed to be briefly exceeded.
Dependency:
Refer to: p1082
Notice:
Continuous operation above a scaling of 100 % is not permitted.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: -
Units group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
19500.000 [rpm]
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
105.00 [%]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 3030
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 3
Func. diagram: 3030
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 1
Func. diagram: 3050
Unit selection: p0505
Expert list: 1
Factory setting
0.000 [rpm]
Access level: 2
Func. diagram: 3050, 3095
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
297