Siemens SINAMICS G150 Manual page 40

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Note:
The drives can only be powered up outside the device commissioning (the inverter enabled). In this case, p0009
must be 0 (Ready) and the individual drive objects must have already gone into operation (p0010).
p0009 = 1: Device configuration
At the first commissioning of the device, after booting, the device is in the "device configuration" state. To start the
internal automatic first commissioning of the drive unit, p0009 should be set to 0 (Ready) after the ID for the actual
topology (r0098) was transferred into the ID for the target topology (p0099). To do this, it is sufficient to set a single
index value of p0099[x] the same as r0098[x]. Before the device has been completely commissioned, no other
parameter can be changed. After the first commissioning was carried out, in this state, when required, other basic
device configuration parameters can be adapted (e.g. the basic sampling time in p0110).
p0009 = 2: Defines the drive type / function module
In this state, the drive object types and/or the function modules can be changed or selected for the individual drive
objects. To do this, the drive object type can be set using p0107[0...15] and the function can be set using
p0108[0...15] (refer to p0101[0...15]).
p0009 = 3: Drive basic configuration
In this state, after the device has been commissioned for the first time, basic changes can be made for the individual
drive objects (e.g. sampling times in p0111, p0112, p0115 and the number of data sets in p0120, p0130, p0140,
p0170, p0180).
p0009 = 4: Data set basic configuration
In this state, after the device has been commissioned for the first time, for the individual drive objects changes can be
made regarding the assignment of the components (p0121, p0131, p0141, p0151, p0161) to the individual data sets
and the assignment of the power unit, motor and encoder to the drive data sets (p0185, ...).
p0009 = 29: Device download
If a download is made using the commissioning software, the device is automatically brought into this state. After the
download has been completed, p0009 is automatically set to 0 (ready). It is not possible to manually set p0009 to this
value.
p0009 = 30: Parameter reset
In order to bring the complete unit into the "first commissioning" state or to load the parameters saved using p0977, to
start, p0009 must be set to this value. p0976 can then be changed to the required value.
p0009 = 50: OA application configuration
In this state, after the device has been commissioned for the first time, changes can be made for the individual drive
objects regarding the activity (p4956) of the OA applications.
p0009 = 55: OA application installation
OA applications can be installed and/or uninstalled in this state.
p0009 = 101: Topology input
In this state, the DRIVE-CLiQ target topology can be entered using p9902 and p9903.
p0009 = 111: Insert drive object
This state allows a new drive object to be inserted using p9911.
p0009 = 112: Delete drive object
This state allows existing drive objects to be deleted using p9912 after the device has been commissioned for the first
time.
p0009 = 113: Change drive object number
This state allows the drive object number of existing drive objects to be changed using p9913 after the device has
been commissioned for the first time.
p0009 = 114: Change component number
This state allows the component number of existing components to be changed using p9914 after the device has
been commissioned for the first time.
p0009 = 115: Parameter download
This state allows the complete device and drive commissioning using the parameter services.
p0009 = 117: Delete component
This state allows components to be deleted using p9917 after the device has been commissioned for the first time.
40
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents