For sensor type "KTY84" (p4100 = 2), the following applies:
If the fault threshold (p4102[1]) is exceeded before the delay time has expired, then fault F35207 is immediately
output.
For sensor type "PTC thermistor" (p4100 = 1), the following applies:
- Alarm and fault threshold simultaneously respond. The fault is only issued after the delay time has expired.
Dependency:
Refer to: r4104
Warning:
Fault F35207 only causes the drive to be shut down if there is at least one BICO interconnection between the drive
and TM31.
Note:
With p4103 = 0 ms, the timer is de-activated and only the fault threshold is effective.
r4104.0...23

BO: TM150 temperature evaluation status / TM150 temp status

TM150
Can be changed: -
Data type: Unsigned32
P-Group: Terminals
Not for motor type: -
Min
-
Description:
Display and binector output for the status for the Terminal Module 150 (TM150).
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Dependency:
Refer to: p4102, p4103, r4105, p4118
r4104.0...1

BO: TM31 temperature evaluation status / TM31 temp status

TM31
Can be changed: -
Data type: Unsigned16
P-Group: Terminals
Not for motor type: -
Min
-
Description:
Display and binector output for the status for the Terminal Module 31 (TM31).
Bit field:
Bit
00
01
Dependency:
Refer to: p4102
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
Channel 0 alarm present
Channel 0 fault present
Channel 1 alarm present
Channel 1 fault present
Channel 2 alarm present
Channel 2 fault present
Channel 3 alarm present
Channel 3 fault present
Channel 4 alarm present
Channel 4 fault present
Channel 5 alarm present
Channel 5 fault present
Channel 6 alarm present
Channel 6 fault present
Channel 7 alarm present
Channel 7 fault present
Channel 8 alarm present
Channel 8 fault present
Channel 9 alarm present
Channel 9 fault present
Channel 10 alarm present
Channel 10 fault present
Channel 11 alarm present
Channel 11 fault present
Signal name
Alarm is present
Fault is present
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Access level: 1
Func. diagram: 9549, 9576
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
FP
9626
9626
9626
9626
9626
9626
9626
9626
9626
9626
9626
9626
9627
9627
9627
9627
9627
9627
9627
9627
9627
9627
9627
9627
FP
-
-
629

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents