2 Parameters
2.2 List of parameters
Value:
0:
1:
2:
3:
4:
5:
6:
Dependency:
Refer to: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198
Note:
The response to the faults F07923 ... F07925 can be set.
This parameter setting has no effect on the production of fault F07936.
p2182[0...n]

Load monitoring speed threshold value 1 / n_thresh 1

VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [rpm]
Description:
Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
Dependency:
The following applies: p2182 < p2183 < p2184
Refer to: p2183, p2184, p2185, p2186
Note:
In order that the load monitoring can reliably respond, the speed threshold p2182 should always be set lower than the
minimum motor speed to be monitored.
p2183[0...n]

Load monitoring speed threshold value 2 / n_thresh 2

VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [rpm]
Description:
Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
Dependency:
The following applies: p2182 < p2183 < p2184
Refer to: p2182, p2184, p2187, p2188
p2184[0...n]

Load monitoring speed threshold value 3 / n_thresh 3

VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [rpm]
Description:
Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
522
Load monitoring disabled
A07920 for torque/speed too low
A07921 for torque/speed too high
A07922 for torque/speed out of tolerance
F07923 for torque/speed too low
F07924 for torque/speed too high
F07925 for torque/speed out of tolerance
Calculated: -
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
210000.00 [rpm]
Calculated: -
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
210000.00 [rpm]
Calculated: -
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
210000.00 [rpm]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 8013
Unit selection: p0505
Expert list: 1
Factory setting
150.00 [rpm]
Access level: 3
Func. diagram: 8013
Unit selection: p0505
Expert list: 1
Factory setting
900.00 [rpm]
Access level: 3
Func. diagram: 8013
Unit selection: p0505
Expert list: 1
Factory setting
1500.00 [rpm]
SINAMICS G130/G150