Bit field:
Bit
00
01
03
15
Dependency:
Refer to: r2197
Note:
Re bit 00:
Alarm A07903 is output when the bit is set with r2197.7 = 0 (n_set <> n_act).
Re bit 01:
When the bit is set, load monitoring is only carried out in the 1st quadrant as a result of the positive characteristic
parameters (p2182 ... p2190).
Re bit 03:
When the bit is set, r2197.1 and r2197.2 are determined using separate hysteresis functions.
Re bit 15:
The bit indicates whether the automatic parameterization (p0340 = 1, p3900 > 0) for the parameters of the extended
monitoring functions was carried out.
If the bit is not set (e.g. when the configuration is activated (p0108.15)), the parameterization is automatically carried
out during booting even if r3925.0 is already 1.
p2150[0...n]

Hysteresis speed 3 / n_hysteresis 3

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency:
Refer to: p2161, r2197, r2199
p2151[0...n]

CI: Speed setpoint for messages/signals / n_set for msg

VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Ramp-up/ramp-down completed" (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency:
Refer to: r2197, r2198, r2199
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
Enable alarm A07903
Load monitoring only in the 1st quadrant
Reserved
Automatic parameterization carried out
(p0340 = 1, p3900 > 0)
1 signal
Yes
Yes
Yes
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
300.00 [rpm]
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: p2000
Max
-
2 Parameters
2.2 List of parameters
0 signal
No
No
No
Access level: 3
Func. diagram: 8010, 8011
Unit selection: p0505
Expert list: 1
Factory setting
2.00 [rpm]
Access level: 3
Func. diagram: 8011
Unit selection: -
Expert list: 1
Factory setting
1170[0]
FP
8011
8013
-
-
517