Re value = 6 (armature short-circuit, internal/DC braking):
The value can only be set for all motor data sets when p1231 = 3, 4.
a) For synchronous motors (p0300 = 2xx, 4xx), an internal armature short-circuit is executed.
b) For induction motors (p0300 = 1xx), a DC braking is initiated.
Re value = 7 (ENCODER (p0491)):
The fault response set in p0491 is executed if applicable.
Note:
IASC: Internal Armature Short Circuit
DCBRK: DC braking
p2102

BI: Acknowledge all faults / Ackn all faults

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned32 / Binary
CU_G150_DP,
P-Group: Messages
CU_G150_PN
Not for motor type: -
Min
-
Description:
Sets the signal source to acknowledge all faults at all drive objects of the drive system.
Note:
A fault acknowledgement is triggered with a 0/1 signal.
p2103[0...n]

BI: 1. Acknowledge faults / 1. Acknowledge

B_INF, VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Messages
Not for motor type: -
Min
-
Description:
Sets the first signal source to acknowledge faults.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
A fault acknowledgement is triggered with a 0/1 signal.
p2103
BI: 1. Acknowledge faults / 1. Acknowledge
CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned32 / Binary
CU_G150_DP,
P-Group: Messages
CU_G150_PN, ENC,
Not for motor type: -
HUB, TB30, TM150,
TM31, TM54F_MA,
Min
TM54F_SL
-
Description:
Sets the first signal source to acknowledge faults.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
A fault acknowledgement is triggered with a 0/1 signal.
p2104[0...n]

BI: 2. Acknowledge faults / 2. Acknowledge

B_INF, VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Messages
Not for motor type: -
Min
-
Description:
Sets the second signal source to acknowledge faults.
Note:
A fault acknowledgement is triggered with a 0/1 signal.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2546, 8060
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2441, 2442,
2443, 2447, 2475, 2546, 9220,
9677, 9678
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2546, 8060
Unit selection: -
Expert list: 1
Factory setting
0
503