Cbe2X Subslot Controller Assignment / Cbe2X Subslot; Cbe2X Ip Address Remote Controller 1 / Cbe2X Ip Rem Ctrl1; Cbe2X Ip Address Remote Controller 2 / Cbe2X Ip Rem Ctrl2; Web Server Configuration / Web Serv Config - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

r8970[0...2]

CBE2x subslot controller assignment / CBE2x subslot

B_INF (PROFINET
Can be changed: -
CBE20),
Data type: Unsigned8
CU_G130_DP
P-Group: -
(PROFINET CBE20),
Not for motor type: -
CU_G130_PN
(PROFINET CBE20),
Min
CU_G150_DP
0
(PROFINET CBE20),
CU_G150_PN
(PROFINET CBE20),
ENC (PROFINET
CBE20), TB30
(PROFINET CBE20),
TM150 (PROFINET
CBE20), TM31
(PROFINET CBE20),
VECTOR_G
(PROFINET CBE20)
Description:
Displays the controller assignment of a PROFINET subslot on the actual drive object.
Index:
[0] = Subslot 2 PROFIsafe
[1] = Subslot 3 PZD telegram
[2] = Subslot 4 PZD supplementary data
Dependency:
Refer to: r8971, r8972
Note:
Example:
If the parameter contains the value 2 in index [1], then this means that subslot 3 is assigned to controller 2.
r8971[0...3]

CBE2x IP Address Remote Controller 1 / CBE2x IP Rem Ctrl1

CU_G130_DP
Can be changed: -
(PROFINET CBE20),
Data type: Unsigned8
CU_G130_PN
P-Group: -
(PROFINET CBE20),
Not for motor type: -
CU_G150_DP
(PROFINET CBE20),
Min
CU_G150_PN
0
(PROFINET CBE20)
Description:
Displays the IP address of the first PROFINET controller connected with the device via CBE20/CBE25.
r8972[0...3]

CBE2x IP Address Remote Controller 2 / CBE2x IP Rem Ctrl2

CU_G130_DP
Can be changed: -
(PROFINET CBE20),
Data type: Unsigned8
CU_G130_PN
P-Group: -
(PROFINET CBE20),
Not for motor type: -
CU_G150_DP
(PROFINET CBE20),
Min
CU_G150_PN
0
(PROFINET CBE20)
Description:
Displays the IP address of the second PROFINET controller connected with the device via CBE20/CBE25.
p8986

Web server configuration / Web serv config

CU_G130_DP,
Can be changed: T
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
-
Description:
Setting to activate and configure the "Web server" function in the drive.
It is possible to access the web server via the integrated Ethernet and PROFINET interfaces of the drive. The
addressing is realized via the set IP address.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
8
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting